Step 6 - Faults and warning codes
POWERXL DM1 SERIES ADJUSTABLE FREQUENCY DRIVES
PUB53696—August 2020 www.eaton.com
Fault
code
Fault name/
description
Fault type
Default
configuration Possible cause
Remedy
98
PI feedback AI
loss
No action
Configurable
The feedback function has a relationship with feedback 1/2 and
the feedback 1/2 source has relationship with AI. The AI signal
range is 1 (20-100%/2-10 V/4-20m A). The AI value is out of
range (AI mode: 0~20 mA, AI < 4 mA or AI > 20 mA, AI mode:
0~10 V, AI < 2 V or AI > 10 V) of PID1 feedback.
Check the AI of PI1 feedback, the AI value
whether is out of range or not, the AI
range shall be 2~10 V ( AI mode is 0~10 V)
or 4~20 mA (AI mode is 0~20 mA).
100
Fieldbus fault
(Fieldbus SMDT
fault)
Fault
Configurable
Smart wire sus fieldbus fault.
Check SmartWire DT card.
101
Option card fault Fault
Configurable
SMDT board hardware fault.
Check SmartWire DT card.
102
External fault
(External fault
from SWD)
Fault
Configurable
External fault from SWD.
Check SmartWire DT card.
111
Profibus firmware
incompatible
Warning
Profibus card firmware is not compatible with MCB firmware.
Check the Profibus card firmware revision.
113
CANOpen
firmware
incompatible
Warning
CANOpen card firmware is not compatible with MCB firmware.
Check the CANOpen firmware revision.
114
SWD firmware
incompatible
Warning
SWD card firmware is not compatible with MCB firmware.
Check the SWD card firmware revision.
115
Fieldbus fault
Fault
Configurable
FieldBus EIP idle fault
Check ethernet IP master programming to
verify proper addressing and ensure idle
communication bit is not set.
117
Pump over cycle Warning
During a period, the times which the drive sleeps and wakes up
exceed a user configurable value.
Check the reason that drive is not stable.
Check why the drive sleeps and wakes up
frequently.
118
Broken pipe
Warning
Configurable
PID feedback is less than broken pipe level and the drive output
frequency is more than broke pipe frequency for delay time.
125
Freq. limit supv.
(Freq. limit)
No action
The output frequency exceeds the range of frequency supervision
limit.
Check the output frequency and check the
setting of frequency supervision limit.
126
Torque limit supv.
(Torque limit)
No action
The motor torque exceeds the range of torque supervision limit.
Check the motor torque and check the
setting of torque supervision limit.
127
Ref. limit supv.
(Ref. limit)
No action
The frequency reference exceeds the range of freq. reference
supervision limit.
Check the frequency reference and
check the setting of frequency reference
supervision limit.
128
Power limit supv.
(Power limit)
No action
The motor power exceeds the range of power supervision limit.
Check the motor power and check the
setting of power supervision limit.
129
Temp. limit supv.
(Temp. limit)
No action
The unit temperature exceeds the range of temperature
supervision limit.
Check the unit temperature and check the
setting of temperature supervision limit.
130
AI limit supv.
(AI limit)
No action
The AI value exceeds the range of AI supervision limit.
Check the AI value and check the setting
of AI supervision limit.
131
Motor current
supv.
(Motor current
limit)
No action
The motor current exceeds the range of current supervision limit Check the motor current and check the
setting of current supervision limit.
132
P
I superv.
No action
The PI1 feedback exceeds the range of PI1 supervision limit.
Check the PI1 feedback and check the
setting of PI1 supervision limit.
133
Fieldbus fault
(Fieldbus web UI
fault)
Fault
Configurable
FieldBus web UI fault.
Check the web connection with RJ45
connector. Verify drive parameters are set
correctly. Check the web UI tool to know
if there is proper request going to drive
or not.