55
Step 5 - Standard application
POWERXL DM1 SERIES ADJUSTABLE FREQUENCY DRIVES
PUB53696—August 2020 www.eaton.com
Table 20. Ethernet communication (Cont.).
P12.4.3
Ethernet IP fault response
ID 2518
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Only in fieldbus control mode - when fieldbus is the control place and Fieldbus fault is active, the drive will fault on loss of
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for ethernet IP communication.
P12.5 - BACnet IP (DM1 PRO only).
P12.5.1
a
BACnet IP UDP port number
ID 1733
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
47,808
Options:
47808 = BAC0;
47809 = BAC1;
47810 = BAC2;
47811 = BAC3;
47812 = BAC4;
47813 = BAC5;
47814 = BAC6;
47815 = BAC7;
47816 = BAC8;
47817 = BAC9;
47818 = BACA;
47819 = BACB;
47820 = BACC;
47821 = BACD;
47822 = BACE; or
47823 = BACF.
Description:
Defines the BACnet UDP port number.
P12.5.2
a
BACnet IP foreign devise
ID 1734
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Disabled; or
1 = Enabled.
Description:
Enables BACNET IP foreign device configuration.
P12.5.3
a
BACnet IP BBMD IP
ID 1735
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0.0.0.0
Description:
Displays the BACnet BBMD IP address.
P12.5.4
a
BACnet IP UDP port
ID 1737
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
47,808
Options:
47808 = BAC0;
47809 = BAC1;
47810 = BAC2;
47811 = BAC3;
47812 = BAC4;
47813 = BAC5;
47814 = BAC6;
47815 = BAC7;
47816 = BAC8;
47817 = BAC9;
47818 = BACA;
47819 = BACB;
47820 = BACC;
47821 = BACD;
47822 = BACE; or
47823 = BACF.
Description:
Displays the BACnet BBMD UDP port number.
P12.5.5
a
BACnet IP registration interval
ID 1738
Minimum value:
0.00
Maximum value:
65,535
Default value:
10
Description:
Defines the registration interval.