52
Step 5 - Standard application
POWERXL DM1 SERIES ADJUSTABLE FREQUENCY DRIVES
PUB53696—August 2020 www.eaton.com
Table 19. Serial communication (Cont.).
P11.4.6
SA bus fault response
ID 1732
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Only in fieldbus control mode - when fieldbus is the control place and fieldbus fault is active. The drive will fault on loss of
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting, if communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for SA bus communication.
P11.5 - SWD.
P11.5.1
Parameter access
ID 2630
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = No permission to read/write on acyclic channel.
1 = Acyclic read/write are allowed on Profibus.
Description:
PNU927 which specifies the operation priority of parameters for acyclic communication.
P11.5.2
a
Parameter data access
ID 2631
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
4
Options:
0 = Local control;
1 = Fieldbus;
2 = Mixed interface;
4 = NET, local on fault; or
5 = Dual mode.
Description:
PNU928 which specifies the control priority of the device for cyclic communication.
P11.5.3
Fault situation counter
ID 2632
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Description:
PNU952 which specifies the fault situation counter.
Only write of 0 is allowed, then the whole fault buffer (actual fault situation and all other fault situations) and the fault message counter
(parameter 944) are erased.
P11.5.4
Board status
ID 2609
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Description:
Status of the board.
B0-DCOM communication fault.
B1-Board HW fault
B2-IO1 24 volt overload fault.
B3-Profibus communication fault.
B4-fieldbus fault.
P11.5.5
Firmware version
ID 2610
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Description:
This parameter provides the firmware version of the SWD.
P11.5.6
Protocol status
ID 2612
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Not configured;
1 = Operational; or
2 = Diagnostics.
Description:
This parameter specifies the protocol status for SWD card.
P11.6 - Bluetooth.
P11.6.1
Bluetooth enabled
ID 1895
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Disabled; or
1 = Enabled.
Description:
Bluetooth enabled.