33
Step 5 - Standard application
POWERXL DM1 SERIES ADJUSTABLE FREQUENCY DRIVES
PUB53696—August 2020 www.eaton.com
Table 8. Monitor (Cont.).
M5.5
PI status
ID 23
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = Stopped;
1 = Running; or
2 = Sleep mode.
Description:
PI status indication, indicates if drive is stopped, running in PI mode, or in PI sleep mode.
M9 - Multi-monitoring.
M9.1
Multi-monitoring
ID 30
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0, 1, 2.
Description:
Displays any three monitoring values in a single screen. The values are selectable via the keypad menu. Multi-monitor page could
see three lines of monitoring values. Up and down keys can be used to select the row and then hitting the left arrow key will allow for
editing the value then by going up and down.
Table 9. Operate mode - O.
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
O1
Output frequency
Hz
1
O2
Freq. reference
Hz
24
O3
Motor speed
rpm
2
O4
Motor current
A
3
O5
Motor torque
%
4
O6
Motor power
%
5
O7
Motor voltage
V
6
O8
DC-link voltage
V
7
O9
Unit temperature
ºC
8
O10
Motor temperature
%
9
R11
b
Keypad reference
Minimum
frequency
Maximum
frequency
Hz
0.00
141
R12
b
PI keypad setpoint 1
PI process
minimum
PI process
maximum
Varies
0.00
1307
b
Parameter value will be set to be default when changing macros.
Table 10. Parameters (Cont.).
P1 - Basic
parameters.
P1.1
b
Minimum frequency
ID 101
Minimum value:
0.00 Hz
Maximum value:
400.00 Hz
Default value:
0.00 Hz
Description:
Defines the lowest frequency at which the drive will operate. This setting will limit other frequency parameter settings.
1 = Fire mode minimum frequency.
2 = Derag.
3 = MPFC staging frequency.
4 = MPFC master fixed frequency.
5 = Prime pump frequency.
6 = Prime pump frequency 2.
.