Appendix A—Fault and Warning Codes
PowerXL DH1 Series Variable Frequency Drives
MN040039EN—April 2018
www.eaton.com
41
9
UnderVoltage
Configurable
Fault
DC link voltage is under the voltage limits
defined:
• Most probable cause: Too low a supply
voltage
• AC drive internal fault
• Defect input fuse
• External charge switch not closed
Note
: This fault is activated only if the drive is
in Run state.
In case of temporary supply voltage break,
reset the fault and restart the AC drive
Check the supply voltage. If it is adequate,
an internal failure has occurred. Contact
the distributor near you
10
Input Phase Superv
Configurable
Fault
Input line phase is missing
Check supply voltage, fuses and cable
11
Output Phase Superv Configurable
Fault
Current measurement has detected that there
is no current in one motor phase
Check motor cable and motor
12
Brake Chopper
Superv
Fault
• No brake resistor installed
• Brake resistor is broken
• Brake chopper failure
Check brake resistor and cabling. If these
are OK, the chopper is faulty. Contact the
distributor near you
13
Drive UnderTemp
Configurable
Warning
Too low temperature measured in power
unit’s heat sink or board. Heat sink
temperature is under –10°C
14
Drive OverTemp
Fault
Too high temperature measured in power
unit’s heat sink or board. Heat sink
temperature is over 90°C
• Check the correct amount and flow of
cooling air
• Check the heat sink for dust
• Check the ambient temperature
• Make sure that the switching frequency
is not too high in relation to ambient
temperature and motor load
15
Motor Stalled
Configurable
No Action
Motor is stalled
Check motor and load
16
Motor Over Temp
Configurable
No Action
Motor is too hot, based on either the drive’s
estimate or on temperature feedback
Decrease motor load. If no motor overload
exists, check the temperature model
parameters
17
Motor Under Load
Configurable
No Action
Condition defined by parameter
P1.9.15~P1.9.17 have been valid longer than
the time defined by P1.9.18
Check load
18
IP Address Conflict
Configurable
Warning
IP setting issue.
Check settings for IP address, verify no
duplicates are on the network.
19
Power Board
EEPROM Fault
Fault
Power board EEPROM fault, memory lost in
EEPROM.
Cycle power to drive. Try updating
software. If issue continues, contact
distributor near you.
20
FRAM Fault
Fault
FRAM data error in FRAM memory.
Cycle power to drive. Try updating
software. If issue continues, contact
distributor near you.
21
S-Flash Fault
warning
Serial flash error, serial flash memory failed. Cycle power to drive. Try updating
software. If issue continues, contact
distributor near you.
25
MCU WatchDog Fault Fault
Watchdog register overflows in MCU
Cycle power to drive. Try updating
software. If issue continues, contact
distributor near you.
26
Start-up Prevent
Fault
The time when Interlock signal activates is
over setting time.
Stop drive and resend start command.
29
Thermistor Fault
Configurable
Fault
Option board or control board thermistor
resistor lager than 4.7K
Thermistor open or short, over temperature
32
Fan Cooling
Fault
Fan is damaged or stalled.
Check fan and fan connected wires, verify
24 Vdc is supplied to fan.