Step 5—Standard Parameter List
PowerXL DH1 Series Variable Frequency Drives
MN040039EN—April 2018
www.eaton.com
29
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Table 32. Drive—P6.2
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P6.2.1
2
Line Start Lockout
2
750
0 = Disabled, No Change
1 = Enable, No Change
2 = Disabled, Changed
3 = Enable, Changed
P6.2.2
2
Fault Reset Start
0
2483
0 = Start/Stop After Fault Reset
1 = Restart After Fault Reset
P6.2.3
1
2
4mA Input Fault
0
306
0 = No Action
1 = Warning
2 = Warning: Previous Freq
3 = Warning: Preset Freq
4 = Fault
5 = Fault, Coast
P6.2.4
1
2
4mA Fault Frequency
0.00
See Par ID 102
Hz
0.00
331
P6.2.5
1
2
External Fault
2
307
See Par ID 308
P6.2.6
1
2
Input Phase Fault
2
332
See Par ID 308
P6.2.7
1
2
Uvolt Fault Response
2
330
See Par ID 308
P6.2.8
1
2
Unit Under Temp Prot
2
1564
See Par ID 308
P6.2.9
1
2
RTC Fault
1
955
See Par ID 308
P6.2.10
1
2
Replace Battery Fault
Response
1
1256
See Par ID 308
P6.2.11
1
2
Replace Fan Fault Response
1
1257
See Par ID 308
P6.2.12
2
Cold Weather Mode
0
2126
See Par ID 1679
P6.2.13
2
Cold Weather Volt. Level
0.0
20.0
%
2.0
2127
P6.2.14
2
Cold Weather Time Out
0
10
min
3
2128
P6.2.15
Cold Weather Password
2129
P6.2.16
Under Temp Fault Override
2130
See Par ID 2118
P6.2.17
2
STO Fault Response
2
2427
0 = No Action
1 = Warning
2 = Fault
Table 33. Communication—P6.3
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P6.3.1
1
2
Fieldbus Fault Response
2
334
0 = No Action
1 = Warning
2 = Fault
3 = Fault, Coast
4 = Warning, Coast
P6.3.2
1
2
OPTCard Fault Response
2
335
See Par ID 308
P6.3.3
1
2
IP Address Confliction Resp
1
1678
See Par ID 308
P6.3.4
1
2
Keypad Comm Fault
Response
2
2157
See Par ID 308