Step 4—Startup Wizard
8
PowerXL DH1 Series Variable Frequency Drives
MN040039EN—April 2018
www.eaton.com
Step 4—Startup Wizard
Startup Wizard
In the
Startup Wizard
, you will be prompted for essential
information needed by the drive so that it can start
controlling your process. In the Wizard, you will need
the following keypad buttons:
Up/Down buttons.
Use these to change value.
OK button.
Confirm selection with this button, and enter into
next question.
Back/Reset button.
If this button was pressed at the first question,
the Startup Wizard will be cancelled.
Once you have connected power to your Eaton PowerXL
frequency converter, and the Startup Wizard is enabled,
follow these instructions to easily set up your drive.
Table 5. Startup Wizard Instructions
Item
Description
1
Startup Wizard
Press OK?
2
Application
0 = Basic
1 = PID
2 = Advanced
3
Language
0 = English
1 =
ѝ᮷
2 = Deutsch
4
Real Time Clock
yy.mm.dd
hh:mm:ss
5
Daylight Saving
0 = Off
1 = EU
2 = US
6
Min Frequency
Min: 0.00Hz
Max: Max Frequency
7
Max Frequency
Min: Min Frequency
Max: 400.00Hz
8
Motor Nom Current
Min: 0.1A
Max: 500.0A
9
Current Limit
Min: Ih*1/10
Max: Ih*2
10
Motor Nom Speed
Min: Ih*1/10
Max: Ih*2
11
Motor PF
Min: 0.30
Max: 1.0
12
Motor Nom Voltage
Min: 180V
Max: 690V
13
Motor Nom Frequency
Min: 30.00 Hz
Max: 400.00 Hz
14
Accel Time 1
Min: 0.1 sec
Max:3000.0 sec
15
Decel Time 1
Min: 0.1 sec
Max:3000.0 sec
16
Hand Control Place
0 = Keypad
1 = I/O Terminal Start 1
2 = I/O Terminal Start 2
3 = Fieldbus