INSTALLATION
EATON
Powerware
®
9125 Two-in-One PDM (5000/6000 VA) User’s Guide
S
164201519 Rev E
www.powerware.com
14
UPS Shutdown
If the UPS is already installed and operating, use the following procedure
to shut down the UPS:
1.
Prepare your equipment for shutdown.
2.
Press and hold the Off
button for approximately three seconds.
The
μ
indicator begins to flash. The UPS switches to Standby
mode (if utility power is available) and removes power from your
equipment.
3.
Unplug the UPS; the UPS shuts down in five seconds. The bar
graph and battery indicators flash briefly prior to shutdown.
4.
Disconnect the power cord from the UPS input connector.
5.
Disconnect the protected equipment power cord from the UPS.
6.
Continue to “Hardwired PDM Installation” on page 19 or
“Plug-Receptacle PDM Installation”on page 28.
Installing the UPS Internal Batteries
C A U T I O N
The UPS battery trays are heavy (28.1 kg/62 lb). A minimum of two people are required to lift
the battery trays into the UPS chassis.
NOTE
For new rack-mounted installations, follow the instructions with the rail kit before
installing the internal batteries.
To install the battery trays into the UPS chassis:
1.
Verify that the battery circuit breaker on the UPS rear panel is in the
OFF position (see Figure 6 on page 18).
2.
Slide the battery trays into the chassis (see Figure 1).
Figure 1. Installing the Battery Trays