INSTALLATION
EATON
Powerware
®
9125 Two-in-One PDM (5000/6000 VA) User’s Guide
S
164201519 Rev E
www.powerware.com
23
PDM Input
Cord
PDM Output
Cord
PDM Output
Circuit Breaker
REPO Connector
Communication Port
USB Port
UPS Battery
Circuit Breaker
Wiring Access Cover
Conduit Landing Plate
Figure 10. UPS and Hardwired PDM Installation
9.
Connect the input and ground wires to the terminal block according
to the PDM model:
S
For the PPDM HW model, see Figure 11 and Table 2.
S
For the PPDM EURO HW model, see Figure 12 and Table 2.
10.
Connect the output and ground wires to the terminal block
according to the PDM model:
S
For the PPDM HW model, see Figure 11 and Table 2.
S
For the PPDM EURO HW model, see Figure 12 and Table 2.
UPS Output Line 2, 208–240V
Load Output Neutral (isolated)
Output
Ground
Source Input Line 1
Source Input Line 2
Input
Ground
Load Output 120V (isolated)
Load Output 120V (isolated)
UPS Output Line 1, 208–240V
E4
1
2
3
4
5
6
7
E5
Figure 11. PPDM HW Model Terminal Block