INSTALLATION
EATON
Powerware
®
9125 Two-in-One PDM (5000/6000 VA) User’s Guide
S
164201519 Rev E
www.powerware.com
18
EBM Installation
C A U T I O N
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and
will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and
firmly.
To install the optional EBM(s):
1.
Verify that all battery circuit breakers are in the OFF (O) position
(see Figure 6).
2.
Plug the EBM cable of the first EBM into the UPS battery
connector.
If additional EBMs are to be installed, plug the EBM cable of the
second cabinet into the battery connector on the first EBM. Repeat
for each additional EBM. Up to four EBMs may be connected to the
UPS.
3.
Continue to the following section, “Hardwired PDM Installation,” or
“Plug-Receptacle PDM Installation” on page 28.
EBM Battery Connector
UPS Battery Connector
EBM Cable
Battery Circuit
Breaker
Battery Circuit Breaker
ON
OFF
UPS
PDM
EBM
Figure 6. Typical UPS Installation with EBM and PDM