INSTALLATION
EATON
Powerware
®
9125 Two-in-One PDM (5000/6000 VA) User’s Guide
S
164201519 Rev E
www.powerware.com
19
Hardwired PDM Installation
W A R N I N G
Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.
C A U T I O N
S
For PDM models with hardwired outputs, overcurrent protection for the output AC
circuit(s) is to be provided by others.
S
For PDM models with hardwired outputs, suitably rated disconnect switches for the
output AC circuit(s) are to be provided by others.
NOTE
Do not make unauthorized changes to the UPS or PDM; otherwise, damage may
occur to your equipment and void your warranty.
The Powerware 9125 hardwired models require a dedicated branch
circuit that meets the following requirements:
S
40A minimum circuit with short circuit and overcurrent protection
S
200–240 Vac
S
Single-phase
S
50/60 Hz
S
The breaker must be wall-mounted and be readily accessible to the
operator
S
Flexible metal conduit (recommended for ease of service and
maintenance)