Electrical Installation
24
Eaton 9355 UPS (20/30kVA) Installation and Operation Manual 164201626—Rev F
www.eaton.com/powerquality
UPS Only Wiring
To hardwire the UPS:
1.
Remove the UPS conduit landing box from the rear panel and retain (see Figure 14).
2.
Punch two holes in the conduit landing box for the input and output conduit using a Greenlee
®
punch or
similar device.
3.
Route the wiring from the back of the UPS, through the wiring tray, to the front of the UPS.
4.
Hardwire the input, output, and ground terminations for the UPS. See Table 1 on page 35 for wiring
specifications.
For a detailed view of the UPS terminal block, see Figure 23 on page 36.
5.
If wiring for dual-feed, remove the jumpers between the input terminal block and the input circuit breaker
(see Figure 23 on page 36).
Wire the second input directly to the input circuit breaker.
6.
Reinstall the UPS connections insulator.
7.
Reinstall the UPS wiring access cover.
8.
Reinstall the UPS conduit landing box in the reversed position (see Figure 14).
9.
Replace the UPS front door (see page 10).
Figure 14. Reversing the UPS Conduit Landing Box