ELECTRICAL INSTALLATION
Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide
S
P-164000200 Rev 4
19
OUTPU
T
NORMA
L
AC SOURCE
N(
L-2
N
1
2
3
4
5
6
7
L-1
L-2)
L-1
120V
120V
240V
Source Input Line 1
Source Input Line 2
Input Ground
Output Line 1
Output Line 2
Output Ground
Output Neutral
UPS Connections
Load Connections
(1 to 3)
(4 to 7)
Figure 10. 9PXPPDM2 I/O Terminal Block
Table 4. 9PXPPDM2 Wiring Specifications
Terminal
Position
9PXPPDM2 Wire Function
Terminal Wire
Size Rating*
Tightening
Torque
1
Source Input Line 1
10–16 mm
2
(8–6 AWG)
1.8
±
0.22 Nm
(16
±
2 lb in)
2
Source Input Line 2
3
Input Ground
6–16 mm
2
(10–6 AWG)
4
Output Line 1
10–16 mm
2
(8–6 AWG)
5
Output Neutral
6
Output Line 2
7
Output Ground
6–16 mm
2
(10–6 AWG)
* Use 8 AWG for 9PXPPDM2 (75
_
C copper wire minimum).
12.
Attach the cable gland to the panel.
13.
Replace the terminal block cover and secure with screw.
14.
Continue to “Voltage Selection” on page 27 to set the voltage
selection.
Содержание PowerPass 9PXPPDM1
Страница 10: ...INTRODUCTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 4...
Страница 12: ...SAFETY Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 6...
Страница 20: ...EQUIPMENT INSTALLATION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 14...
Страница 40: ...VOLTAGE SELECTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 34...
Страница 50: ...STARTUP Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 44...
Страница 54: ...MAINTENANCE BYPASS Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 48...
Страница 62: ...SERVICE AND SUPPORT Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 56...