23
Table 5. 9PXTFMR11 Wiring Specifications
Terminal
Position
Wire Function
Terminal Wire
Size Rating*
Tightening
Torque
9PXTFMR11
1
Source Input Line 1
6 AWG
1.8
±
0.22 Nm
(16
±
2 lb in)
2
Source Input Line 2
6 AWG
3
Input Ground
6 AWG
4
Output Line 1
6 AWG
5
Output Neutral
6 AWG
6
Output Line 2
6 AWG
7
Output Ground
6 AWG
* Use 6 AWG for 9PXTFMR11 (90
_
C copper wire minimum).
11.
Attach the cable gland to the panel.
12.
Replace the terminal block cover and secure with screw.
13.
Continue to “Voltage Selection” on page 27 to set the voltage
selection.
9PXPPDM1 and 9PXTFMR5 Electrical Installation
This section provides terminal block wiring requirements and electrical
installation procedures for the 9PXPPDM1 and the 9PXTFMR5 models.
Requirements
C
A
U
T
I
O
N
The 9PXPPDM1 and 9PXTFMR5 models require a 30A circuit with short circuit and
overcurrent protection.
Содержание PowerPass 9PXPPDM1
Страница 10: ...INTRODUCTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 4...
Страница 12: ...SAFETY Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 6...
Страница 20: ...EQUIPMENT INSTALLATION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 14...
Страница 40: ...VOLTAGE SELECTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 34...
Страница 50: ...STARTUP Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 44...
Страница 54: ...MAINTENANCE BYPASS Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 48...
Страница 62: ...SERVICE AND SUPPORT Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 56...