ELECTRICAL INSTALLATION
Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide
S
P-164000200 Rev 4
18
Remove Screw
OUTPUT
OUTPU
T
L
AC SOURCE
NORMALAC SOURCE
Punch Out
Knock-out
Holes
Normal AC
Source
Output
NORMA
Figure 9. Removing the Terminal Block Cover
6.
Punch out the pre-cut knock-out holes for the input and output
conduit.
7.
Pull the input and output wires through separate conduit, leaving
approximately 0.5m (2 ft) of exposed wire. Attach a flexible metal
fitting to the end of each conduit.
8.
On the UPS, insert each conduit through a wiring access entry.
Strip 9 mm (0.35
”
) of insulation from the end of each incoming wire.
9.
On the 9PXPPDM2 terminal block, wire the UPS connections
(terminals 1–3) and attach the cable gland to the panel (see
Figure 10 and Table 4).
10.
To wire the load connections (terminals 4–6), observe the following:
S
Connect 4 and 6 (line to line) for 240V
S
Connect 5 and 6 (line to neutral) for 120V
S
Connect 4 and 5 (line to neutral) for 120V
11.
Connect 7 (ground).
Содержание PowerPass 9PXPPDM1
Страница 10: ...INTRODUCTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 4...
Страница 12: ...SAFETY Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 6...
Страница 20: ...EQUIPMENT INSTALLATION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 14...
Страница 40: ...VOLTAGE SELECTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 34...
Страница 50: ...STARTUP Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 44...
Страница 54: ...MAINTENANCE BYPASS Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 48...
Страница 62: ...SERVICE AND SUPPORT Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 56...