Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide
S
P-164000200 Rev 4
15
Chapter 4
Electrical Installation
This chapter provides electrical installation instructions for the Eaton 9PX
PowerPass Distribution Modules (PPDMs) and 9PX Transformers.
W
A
R
N
I
N
G
Risk of electrical shock. Only qualified service personnel (such as a licensed electrician) shall
perform the electrical installation.
C
A
U
T
I
O
N
S
To reduce the risk of fire, unit input connect only to a circuit provided with branch circuit
overcurrent protection (30A for 9PXPPDM1, 9PXPPDM2, and 9PXTFMR5; 80A for
9PXTFMR11) in accordance with the National Electrical Code
®
(
NEC
®
)
, ANSI/NFPA 70 or
your local electrical code.
S
For 9PXPPDM2 and 9PXTFMR11 only: For models with terminal-block wired outputs,
overcurrent protection for the output AC circuit(s) is to be provided by others.
S
For 9PXPPDM1 and 9PXTFMR5 only: For pluggable equipment:, the socket-outlet shall be
installed near the equipment and shall be easily accessible.
S
Disconnection Device. For 9PXPPDM2, a disconnect switch shall be provided by others
for AC input and output circuit.
S
Disconnection Device. For 9PXTFMR11, the disconnection device of the UPS used with
this power distribution module also serves as the AC input disconnection device of this
power distribution module. A disconnect switch shall be provided by others for AC output
circuit.
NOTE
Do not make unauthorized changes to the 9PX UPS, 9PX PPDM, or 9PX Transformer
models. Otherwise, damage may occur to your equipment and void your warranty.
Table 3 lists the recommended input circuit breaker rating for 9PX
PPDMs.
Table 3. Recommended Input Circuit Breaker Rating for 9PX PPDMs
9PX PPDM
Input Circuit Breaker Rating
9PXPPDM1
30A
9PXPPDM2
30A
Содержание PowerPass 9PXPPDM1
Страница 10: ...INTRODUCTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 4...
Страница 12: ...SAFETY Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 6...
Страница 20: ...EQUIPMENT INSTALLATION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 14...
Страница 40: ...VOLTAGE SELECTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 34...
Страница 50: ...STARTUP Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 44...
Страница 54: ...MAINTENANCE BYPASS Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 48...
Страница 62: ...SERVICE AND SUPPORT Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 56...