Instruction Booklet 

IB015001EN

Effective June 2015

Power Xpert Solar DC 

breaker recombiner 

  

EATON 

www.eaton.com

Preparing Recombiner for insulation/megger testing
Devices installed with control power fusing

Devices that require control power fusing can be easily damaged 

beyond repair if not disconnected during the testing phase . 
These devices include, but are not limited to, customer metering 

equipment and communication equipment . 

 WARNING

DISCONNECT POWER AT SOURCE BEFORE REMOVING OR INSTALLING 

FUSES. HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY OR DEATH.

Prior to testing the Recombiner, turn off all control power devices 

in the Recombiner to prevent damage to components . The control 

power may be turned off by using the control power switch or by 

removing the fuses . Components that use power supplies include 

customer metering and certain breaker accessories, and these must 

be isolated before testing . 

Pre-energizing Recombiner insulation testing

Exercise extreme care to prevent the equipment from being 

connected to the power source while tests are being conducted.

Prior to energizing the Recombiner, perform a Megger or DC test of 

the Recombiner’s insulation . With the phases isolated from ground 

and the circuit breakers open, conduct electrical insulation resistance 

tests from phase-to-phase, phase-to-ground . Retain results for use 

to compare to results produced in the future . A form for recording 

test results is provided in the appendix of this document . Prior 

to testing, remove all control power fusing and connections to 

products, which will be damaged in this test . See above .

 WARNING

TO PREVENT DAMAGE TO CONTROL CIRCUITS WHEN MEGGERING 

RECOMBINER, ISOLATE CIRCUITS FROM RECOMBINER SYSTEM BEFORE 

BEGINNING THE MEGGER OPERATION. BE SURE TO RECONNECT THOSE 

CIRCUITS AFTER MEGGER TESTS ARE COMPLETED.

DO NOT USE AC DIELECTRIC TESTING.

 WARNING

DO NOT USE AC DIELECTRIC/MEGGER TESTING.

A test resulting in readings at or above 1 mega ohm is satisfactory .

Post-testing

After testing, and with the Recombiner de-energized, reconnect all 

devices, control fusing, and disconnects removed prior to testing . 

Securing the Recombiner

Reinstall all side covers, deadfront plates, doors, and trim parts on 

the Recombiner using hardware supplied by the manufacturer .
Take caution that conductors are not pinched between parts when 

installing the deadfront, cover plates, side sheets, and filler plates . 

All parts should be aligned and secured when installed . Do not leave 

holes or gaps in the deadfront construction . Clean up any debris in 

and around the Recombiner .

 

Energizing Recombiner

 WARNING

HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY OR DEATH.

 WARNING

ONLY THOSE PROFESSIONALS TRAINED AND QUALIFIED ON ELECTRICAL 

RECOMBINERS SHOULD INSTALL AND/OR SERVICE THIS EQUIPMENT. 

Extreme hazards can exist when energizing Recombiners . Take 

all precautions necessary to protect people and property when 

energizing the equipment . Short circuits and ground faults may exist 

as a result from inadequate installation . Short circuits and ground 

faults within the Recombiner can cause catastrophic damage, injury, 

and death . 

1. 

Prior to energizing the Recombiner, turn OFF all overcurrent 

devices and loads internal to the Recombiner plus downstream 

equipment . 

2. 

Verify and follow the sequence of energizing circuits and loads . 

Verify phase connections .

3. 

Turn ON each overcurrent device .

Maintenance

It is essential to maintain the equipment in satisfactory condition .
To ensure continued quality service, a systematic maintenance 

schedule is vital . Facility operation and local conditions vary to such 

an extent that the schedule must be prepared to suit the conditions . 

The maintenance schedule for individual devices, such as circuit 

breakers and so on, should be based upon recommendations 

contained in the individual instruction leaflet for each device . 

Inspection and test operations should be coordinated with an overall 

testing program to result in the least operating inconvenience and 

system shutdowns . 

 DANGER

HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY OR DEATH. 

DE-ENERGIZE RECOMBINER PRIOR TO SERVICING.

 WARNING

ONLY THOSE PROFESSIONALS TRAINED AND QUALIFIED ON ELECTRICAL 

RECOMBINERS SHOULD INSTALL AND/OR SERVICE THIS EQUIPMENT. 

Prior to performing any maintenance on the Recombiner,  

first de-energize the Recombiner at the sources. Use lockout/ 

tagout precautions as prescribed in OSHA, NFPA 70E, and other 

safety manuals.

The Recombiner should be given a thorough maintenance  

check annually .

Exercise extreme care to prevent the equipment from being 

connected to the power source while tests are being conducted.

Содержание Power Xpert

Страница 1: ...biner Contents Description Page Safety measures 2 Pre installation receiving handling and storage 3 Pre installation preparation 5 Considerations for seismic qualified installations 5 Electrical conne...

Страница 2: ...D WITHOUT THE SAFETY ALERT SYMBOL INDICATES A POTENTIALLY HAZARDOUS SITUATION THAT IF NOT AVOIDED CAN RESULT IN PROPERTY DAMAGE Eaton s liability for any errors or omissions in this document is limite...

Страница 3: ...t from dust dirt moisture and damage until ready for installation The Recombiner should remain attached to its shipping skid until it has been moved into its final installation position Handling WARNI...

Страница 4: ...which are top heavy equipment The forks or blades of the forklift must run through the entire Recombiner shipping length and be extended to the outermost sides of the wooden shipping skids see Figure...

Страница 5: ...ional requirements The entire area around the Recombiner should be thoroughly cleaned of all debris Considerations for seismic qualified installations Recombiners are seismic qualified and in seismica...

Страница 6: ...talled cables wire used to connect components between sections from damage when moving Recombiner sections into place An outdoor multi section Recombiner will ship with uninstalled intermediate roof c...

Страница 7: ...type washer see Figure 11 Holes are provided on the side of each Recombiner section for this purpose Three holes are located on the side of each section toward the front and back see Figure 12 Figure...

Страница 8: ...BUS OR COMPONENTS To accommodate future serviceability the manufacturer recommends that the head of the carriage bolt be mounted from the rear of the Recombiner for FRONT ACCESSIBLE Recombiners with t...

Страница 9: ...r of the crimp tool Once the lug is affixed to the conductor reinstall the lug on the lug pad using the existing hardware Torque hardware using information provided on Recombiner labeling Refer to App...

Страница 10: ...s on the Recombiner using hardware supplied by the manufacturer Take caution that conductors are not pinched between parts when installing the deadfront cover plates side sheets and filler plates All...

Страница 11: ...T AC DIELECTRIC MEGGER TESTING DAMAGE TO COMPONENTS WILL OCCUR A test resulting in readings at or above 1 mega ohm is satisfactory Compare these test readings with prior readings and retain with previ...

Страница 12: ...ts such as short circuits and overloads until the cause of the event has been identified and corrected After the event has been rectified test equipment per the maintenance process described in this p...

Страница 13: ...the part Drawing numbers Rating of part s Electrical equipment has a limited life span As such the manufacturer cannot guarantee the availability of obsolete equipment or parts Equipment replacement m...

Страница 14: ...VE POSITIVE Ground NEGATIVE Ground Date All overcurrent devices closed Phase to phase connections Phase to ground connections POSITIVE NEGATIVE POSITIVE Ground NEGATIVE Ground Notes Date All overcurre...

Страница 15: ...s Secondary control wiring Clean ventilation Date Checklist 3 Notes and actions taken Cleaning Bus and cable connections Insulation inspection Overcurrent device inspection Controllers Other protectiv...

Страница 16: ...eir respective owners Instruction Booklet IB015001EN Effective June 2015 Power Xpert Solar DC breaker recombiner Eaton 1000 Eaton Boulevard Cleveland OH 44122 United States Eaton com 2015 Eaton All Ri...

Отзывы: