Controllers and other devices

Individual devices should be maintained according to the specific 

instructions supplied for each device . Remove dust and dirt from 

exterior with a dry lint-free cloth . Unless specifically instructed in the 

individual device instruction leaflet, do not attempt to open sealed 

cases or containers .

 WARNING

NEVER USE COMPRESSED AIR TO CLEAN OR BLOW OUT DEBRIS OR DUST 

IN RECOMBINERS.

Secondary wiring

Check all wiring connections for tightness and at all terminal blocks . 

Check all secondary wiring connections to ensure that they are 

properly connected to the Recombiner ground bus, where indicated . 

Look for broken wire strands and pinched or damaged insulation .

Ventilation

Check all grills and ventilation ports for obstructions and 

accumulations of dirt . Clean ventilation ports, if necessary . For 

Recombiners installed outdoors, inspect the air space under the 

Recombiner to be sure that it is clean and clear of debris, leaves, 

and obstructions .

Records

It is essential to maintain the equipment in satisfactory condition .
Maintain a permanent record of all maintenance activities and 

testing for future reference (see 

Appendix B

) .

The condition of each Recombiner should be recorded as a guide 

for anticipating the need for any replacement parts or components 

or special attention at the next regular maintenance period . It is 

recommended that a series of inspections be made at quarterly 

intervals until the progressive effects of local conditions can be 

analyzed to determine a regular schedule . 

Recombiner events and service interruptions
Short-circuits and overloads

 WARNING

DO NOT ATTEMPT TO RE-ENERGIZE RECOMBINER OVERCURRENT DEVICES 

AFTER ELECTRICAL EVENTS, SUCH AS SHORT CIRCUITS, GROUND FAULTS, 

AND OVERLOADS, UNTIL THE CAUSE OF THE EVENT HAS BEEN IDENTIFIED 

AND CORRECTED.

A thorough assessment, identification, and correction of the 

event origin must be completed . An additional assessment of the 

conductor insulation and other insulating materials should be made . 

Replace all damaged insulation materials, conductors, and over- 

current devices . Original Recombiner parts, insulators, insulation 

material, and overcurrent devices must be replaced with renewal 

parts from Eaton (see “Renewal parts,” 

page 12

) .

Do not attempt to re-energize Recombiner overcurrent 

components after electrical events, such as short circuits and 

overloads, until the cause of the event has been identified  

and corrected. 

After the event has been rectified, test equipment per the 

maintenance process described in this publication . 

Physical damage

Any physical damage to the Recombiner that occurs after the 

Recombiner is installed must be corrected . A thorough inspection, 

which includes the exterior enclosure and deadfront, plus interior 

components in the damaged portion of the Recombiner, should be 

conducted . Replace all damaged parts and components . Ensure 

that there are no gaps in the Recombiner enclosure that could 

cause exposure to live parts . Contact Eaton for renewal parts and 

assistance .
After the physical damage has been corrected, test equipment per 

the maintenance process described in this publication .

Water damage

 DANGER

WET RECOMBINERS PRESENT A HAZARDOUS CONDITION AND MAY 

CAUSE INJURY OR DEATH. DE-ENERGIZE POWER TO ALL EQUIPMENT 

BEFORE SERVICING.

DO NOT WORK ON SURFACES OR FLOORS WHERE THERE IS 

STANDING WATER.

 DANGER

DO NOT WORK ON RECOMBINERS OR ENTER AREAS THAT HAVE 

STANDING WATER. DE-ENERGIZE ALL EQUIPMENT IN AREAS WITH 

STANDING WATER.

DO NOT WORK ON WET ENERGIZED ELECTRICAL EQUIPMENT.
Major accumulation

 of water or moisture on any part of the 

Recombiner can cause catastrophic damage to the Recombiner . If a 

Recombiner has been submerged by more than 2 inches or where 

running or standing water has had contact with current-carrying 

parts, it has sustained significant damage . 

 WARNING

RECOMBINER COMPONENTS, INCLUDING CIRCUIT BREAKERS, FUSIBLE 

SWITCHES, AND SO ON, SUBJECTED TO WATER OR MOISTURE MAY BE 

RENDERED UNSAFE. REPLACEMENT IS REQUIRED.

The Recombiner and its components may be damaged beyond 

repair and may need replacement . 

1.  Do not attempt to clean or repair water-damaged equipment 

or components. 

2.  De-energize the Recombiner at its source.
3.  Do not energize. 
4.  Contact Eaton for replacement. 

Minor

 

accumulations

 of moisture, such as condensation, over a 

short period of time, may be corrected using heat . 
De-energize Recombiner .
Apply approximately 250 watts per vertical section for a sufficient 

period of time until the moisture disappears, then remove all heat 

sources and materials used for drying .
Inspect for damage to components and any corrosion . If any  

damage or corrosion is present, contact Eaton . DO NOT 

RE-ENERGIZE RECOMBINER .
After the Recombiner has dried completely, remove all materials and 

tools from the equipment . Inspect all connections for damage and 

torque . Reinstall all covers, fillers, deadfront assemblies, and side 

sheets . Conduct Recombiner insulation resistance testing described 

in this publication .

Содержание Power Xpert

Страница 1: ...biner Contents Description Page Safety measures 2 Pre installation receiving handling and storage 3 Pre installation preparation 5 Considerations for seismic qualified installations 5 Electrical conne...

Страница 2: ...D WITHOUT THE SAFETY ALERT SYMBOL INDICATES A POTENTIALLY HAZARDOUS SITUATION THAT IF NOT AVOIDED CAN RESULT IN PROPERTY DAMAGE Eaton s liability for any errors or omissions in this document is limite...

Страница 3: ...t from dust dirt moisture and damage until ready for installation The Recombiner should remain attached to its shipping skid until it has been moved into its final installation position Handling WARNI...

Страница 4: ...which are top heavy equipment The forks or blades of the forklift must run through the entire Recombiner shipping length and be extended to the outermost sides of the wooden shipping skids see Figure...

Страница 5: ...ional requirements The entire area around the Recombiner should be thoroughly cleaned of all debris Considerations for seismic qualified installations Recombiners are seismic qualified and in seismica...

Страница 6: ...talled cables wire used to connect components between sections from damage when moving Recombiner sections into place An outdoor multi section Recombiner will ship with uninstalled intermediate roof c...

Страница 7: ...type washer see Figure 11 Holes are provided on the side of each Recombiner section for this purpose Three holes are located on the side of each section toward the front and back see Figure 12 Figure...

Страница 8: ...BUS OR COMPONENTS To accommodate future serviceability the manufacturer recommends that the head of the carriage bolt be mounted from the rear of the Recombiner for FRONT ACCESSIBLE Recombiners with t...

Страница 9: ...r of the crimp tool Once the lug is affixed to the conductor reinstall the lug on the lug pad using the existing hardware Torque hardware using information provided on Recombiner labeling Refer to App...

Страница 10: ...s on the Recombiner using hardware supplied by the manufacturer Take caution that conductors are not pinched between parts when installing the deadfront cover plates side sheets and filler plates All...

Страница 11: ...T AC DIELECTRIC MEGGER TESTING DAMAGE TO COMPONENTS WILL OCCUR A test resulting in readings at or above 1 mega ohm is satisfactory Compare these test readings with prior readings and retain with previ...

Страница 12: ...ts such as short circuits and overloads until the cause of the event has been identified and corrected After the event has been rectified test equipment per the maintenance process described in this p...

Страница 13: ...the part Drawing numbers Rating of part s Electrical equipment has a limited life span As such the manufacturer cannot guarantee the availability of obsolete equipment or parts Equipment replacement m...

Страница 14: ...VE POSITIVE Ground NEGATIVE Ground Date All overcurrent devices closed Phase to phase connections Phase to ground connections POSITIVE NEGATIVE POSITIVE Ground NEGATIVE Ground Notes Date All overcurre...

Страница 15: ...s Secondary control wiring Clean ventilation Date Checklist 3 Notes and actions taken Cleaning Bus and cable connections Insulation inspection Overcurrent device inspection Controllers Other protectiv...

Страница 16: ...eir respective owners Instruction Booklet IB015001EN Effective June 2015 Power Xpert Solar DC breaker recombiner Eaton 1000 Eaton Boulevard Cleveland OH 44122 United States Eaton com 2015 Eaton All Ri...

Отзывы: