10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.3 Profinet
148
PXR Electronic trip unit
01/21 MN012005EN
www.eaton.com
11
Settings - instan-
taneous short-
circuit release (I
i
)
R/W
Unsigned
Settings - instantaneous short-circuit release
(I
i
= n x I
n
)
NZM PXR20: R
NZM PXR25: R/W
NZM PXR20:
20: 2
30: 3
40: 4
50: 5
60: 6
70: 7
80: 8
90: 9
100: 10
110: 11
120: 12
140: 14
160: 16
180: 18
The following applies to the NZM PXR25:
The value range [20 - 180] corresponds to 2 to 18,
in increments of 0.1 (1 for values)
A
12
0
0x0001
Type of ground-
fault detection
R
Unsigned
Type of ground-fault detection: 0 = differential
current detection
–
13
0 - 1
0x0003
Settings - functio-
ning of the
ground-fault
protection
R/W
Encoded
Type of ground-fault protection
0: trip
1: alarm
2: OFF
–
14
0
0x0001
ground-fault
release - wave-
form
R/W
Encoded
Ground-fault release - waveform:
0: flat
1: I
2
t
–
15
Settings - ground-
fault release (I
g
)
R/W
Unsigned
Settings - ground-fault release (I
g
= n x I
n
)
NZM PXR20: R
NZM PXR25: R/W
NZM PXR20:
20: 0.2
30: 0.3
40: 0.4
60: 0.6
80: 0.8
100: 1.0
The value range [20 - 100] corresponds to 0.2 to
1.0, in increments of 0.1 (10 for values)
A
Index
(Hex)
Bit field
Mask
field
Setpoint name
R/W
Format
Description or value