![Eaton Power Xpert PXR 10 Скачать руководство пользователя страница 97](http://html1.mh-extra.com/html/eaton/power-xpert-pxr-10/power-xpert-pxr-10_manual_4153055097.webp)
10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.1 EtherNet/IP
PXR Electronic trip unit
01/21 MN012005EN
www.eaton.com
93
In setting group 0, the maintenance mode setting (instance 8) can be divided
into two parts. The high byte is read only and is used for the status indication
of the maintenance mode, the comprehensive results of the maintenance
mode rotary switch, the secondary terminal and the communication settings.
The low byte can be configured and is used to indicate the maintenance
mode settings via the communication port.
The respective protection settings may vary according to the size, type and
rated operational current of the release.
8
8
0x0100
Maintenance
mode: state
R
Encoded
0: off
1: on
–
BBE
0x0001
Maintenance
mode: remote
control
R/W
Encoded
0: off
1: on
–
9
2 - 0
0x0007
Maintenance
mode: Trip setting
R/W
Encoded
1: 2.5 x I
n
2: 4 x I
n
3: 6 x I
n
4: 8 x I
n
5: 10 x I
n
A
11
0
0x0001
Direction of
incoming supply
R/W
Encoded
0: forward
1: reverse
Note:
only available on the PXR25
–
12
0
0x0001
Sign convention
R/W
Encoded
Sign convention:
0: IEC
1: IEEE
2: IEEE old
–
13
Power demand
window
R/W
Encoded
Power demand:
0: fixed
1: sliding
–
14
Power demand
interval
R/W
Encoded
Power demand:
5 - 60 min (1 min increments)
–
17
Configuration of
relay 1
R/W
Encoded
Configuration of relay 1 and relay 2:
–
18
Configuration of
relay 2
R/W
Encoded
–
20
Phase sequence –
phase L1 (A)
R/W
Encoded
Phase L1 (A)
0: counterclockwise
1: clockwise
–
23
0xBCC
Alarm - Residual
Life
R/W
Encoded
Range: 50 - 100, step size 1, default value: 75
Alarm level value 100
≙
0 % residual life
Alarm level value 75
≙
25 % residual life
Formula for conversion:
Alarm level expressed as a percentage
= 100 - point value
–
Instance
Bit
field
Mask
field
Setpoint name
R/W
Format
Description or value
Unit
Содержание Power Xpert PXR 10
Страница 4: ...II ...
Страница 40: ...4 Protection settings 4 12 Residual life indicator 36 PXR Electronic trip unit 01 21 MN012005EN www eaton com ...
Страница 166: ...11 Troubleshooting 160 PXR Electronic trip unit 01 21 MN012005EN www eaton com ...
Страница 170: ...12 PXR25 Navigation menu 164 PXR Electronic trip unit 01 21 MN012005EN www eaton com ...