10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
PXR Electronic trip unit
01/21 MN012005EN
www.eaton.com
127
Table 72: Minor alarm event - EtherCAT
2147
Unsigned 32
R
I
L1
(IA)
A
2148
Unsigned 32
R
I
L2
( IB)
A
2149
Unsigned 32
R
I
L3
( IC)
A
214A
Unsigned 32
R
I
N
(IN)
A
214C
Unsigned 32
R
I
G
(IG residual)
A
214D
Unsigned 16
R
U
L1-L2
(VAB)
V
214E
Unsigned 16
R
U
L2-L3
(VBC)
V
214F
Unsigned 16
R
U
L3-L1
(VCA)
V
2150
Unsigned 16
R
U
L1-N
(VAN)
V
2151
Unsigned 16
R
U
L2-N
(VBN)
V
2152
Unsigned 16
R
U
L3-N
(VCN)
V
2153
Signed 32
R
Active 3-phase power
W
2154
Signed 32
R
Reactive 3-phase power
VAR
2155
Unsigned 32
R
Apparent 3-phase power
VA
2156
Signed 32
R
Active power demand
W
2157
Signed 32
R
Reactive power demand
VAR
2158
Unsigned 32
R
Apparent power demand
VA
215A
Unsigned 32
R
Frequency
1/10 Hz
215C
Unsigned 32
R
Number of operations
–
215D
Bit 31 – Bit 0
R
Binary status with valid bits
–
Index
[Hex]
Format
R/W
Description
(historical event overview)
213C
Encoded
R/W
Event type:
summary = 0x81FF
213D
Signed 32
R
Earliest event ID
213E
Signed 32
R
Latest event ID
213F
Signed 32
R/W
Requested event ID
2140
Signed 32
R
Previous event ID
2141
Signed 32
R
Next event ID
2142
Date/time
R
Date/time
2143
Encoded
R
Data format:
Small alarm: 0x0006
2144
Bit 0
R
Valid bits of the object
2145
Encoded
R
Status reason (primary, secondary, reason code)
Index
[Hex]
Format
R/W
Description
(historical event overview)
Unit
Содержание Power Xpert PXR 10
Страница 4: ...II ...
Страница 40: ...4 Protection settings 4 12 Residual life indicator 36 PXR Electronic trip unit 01 21 MN012005EN www eaton com ...
Страница 166: ...11 Troubleshooting 160 PXR Electronic trip unit 01 21 MN012005EN www eaton com ...
Страница 170: ...12 PXR25 Navigation menu 164 PXR Electronic trip unit 01 21 MN012005EN www eaton com ...