Page 8
IB02601007E
www.eaton.com
2 Quick Start Guide for the Meter Module
2.2. Power Supply Connections
1. Connect the Power Supply (PXMPS-1)
The Meter Module is powered using a 100-240Vac or 110-250Vdc (PXMPS-1) standard
power supply.
• PS1-3 connected to ground
• PS1-2 connected to Neutral (Vac) or (-)Vdc
• PS1-1 connected to Line (Vac) or (+) Vdc
Fabricate a power cord of suitable length and connect to the power supply via the Power
Supply Connection shown in
Figure 1
. (Note: The Green Health LED should blink at a
slow rate (once per second). If it blinks at a faster rate, see the Troubleshooting chapter in
the manual. The Red Status LED will blink if unacknowledged or uncleared events exist.
PXMPS-1 Card
Power Supply
Connection
PS1-3
PS1-2
PS1-1
Health &
Status
LEDs
Figure 1:
Meter Module Power Supply Connection
& LED Locations
Power
LED
Protective Earth
Ground