2 Quick Start Guide for the Meter Module
2.4. Establishing Communications between the Meter Module and the Optional Graphic Display Module
1.
Establishing communication between the Graphic Display Module and Meter Module:
A.
Using an RS485 cable, connect COM 0 (
Figure 4
) on the back of the Display Module
to COM 0 (
Figure 5
) found on the Meter Module (RS485 Comms). See table below and
the Cable Specifications Table for wiring.
Display
PXCM
Description
Terminal Cable Terminal
DA
DG1-1 TP CM5-1
DB
DG1-2 TP CM5-2
SH
DG1-3 SDW CM5-3
TP=Twisted Pair
SDW = Shield Drain Wire
B.
Connect CM6 (
Figure 5
) located on the CM card to DG2 (
Figure 4
) on the Display
Module to supply power (24V) to the Display Module. See table below for wiring.
Display
PXCM
Description
Terminal Cable Terminal
SH
DG2-1 OSCS CM6-1
24+
DG2-2 TP
CM6-2
COM
DG2-3 TP CM6-3
Gnd
DG2-4 To local panel ground
OSCS=Optional Separate Cable Shield
(OSCS used for separate power and data cables)
Figure 3:
CT & VT Connections
VX Connections
CT Connections
VT Connections