UPS INSTALLATION PLAN AND UNPACKING
Power Xpert
9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual
164201710 Rev 7
www.eaton.com/powerquality
3-18
C
A
U
T
I
O
N
On all 9395 models that will be fed by a site generator at any time it is recommended to have an “On
Generator” sensing input connected and proven functional. This allows the UPS to optimize its operation
with the generator. This function includes reduced input current and battery current limits, slower walk-in to
ease the load step on the generator initially, and HIGH ALERT mode for ESS and VMMS operation.
HIGH ALERT mode is desired because any loads with a leading power factor will not be seen by the
generator. Rectifier operation will be much softer while on generator thereby increasing overall system
stability.
3.2.5
Distributed Bypass Power Wiring Preparation
NOTE
For full-rated operation of a Distributed Bypass System when in Bypass or ESS mode, the line
frequency impedance of all conduction paths must be equal when assessed from the point where the Bypass
Power Source connects to the System Switchgear to the point where the Common Load connects to the
System Switchgear.
Read and understand the following notes while planning and performing the
installation:
All distributed bypass UPS rectifier inputs must come from one source and all
bypass input feeds must come from one source.
All UPSs in the distributed bypass system must contain the same number of
UPMs. Mixed UPS kVA ratings are not permitted.
Distributed bypass UPS input wiring size requirements and output wiring size
requirements from the UPSs to the tie cabinet or distribution panel are the same as
listed in Table 3‐4 on page 3-8 and Table 3‐5 on page 3-10.
If the load requires a neutral, a bypass source neutral must be provided.
In the case of parallel Distributed Bypass configurations, wiring for the common
system neutral reference will also be connected to E12 of each module and this
common system neutral reference wiring will be routed to the output switchgear
cabinet and connected to an isolated / ungrounded bus which is common with the
wiring from the E12 terminal of all other paralleled modules of the Distributed
Bypass system.
DO NOT install both a source neutral and a bonding jumper. See Table 3‐7 for
neutral bonding jumper wire sizes. The bonding jumper must be copper wire.
Eaton UPS systems are designed to operate with two optional ground schemes.
Both configurations comply with international safety regulations (as seen on the
UPS name plate).
-
1. Internal reference generated through an earth reference. Ground current will
be equal to or less than 5% of the unit rating. This takes the form of a UPS N
bus to ground bond wire. This configuration is confirmed by reviewing the units
CTO number.
-
2. Internally generated reference which avoids ground current. By locating the
center reference inside the three phase conductors, the relationship between
the UPS source and the UPS output is maintained. This is an internal UPS
function and requires no additional work on the part of the installer or user. This
configuration is confirmed by reviewing the units CTO number.
Содержание Power Xpert 9395 Plus
Страница 1: ...Power Xpert 9395 Plus 1 UPS 225 275 kVA Installation and Operation Manual...
Страница 2: ......
Страница 3: ...Power Xpert 9395 Plus 1 UPS 225 275 kVA Installation and Operation Manual...
Страница 215: ......
Страница 216: ...1642017107 164201710 7...