UPS OPERATING INSTRUCTIONS
Power Xpert
9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual
164201710 Rev 7
www.eaton.com/powerquality
7-26
7.3.21
Single UPM Restart
To restart a single UPM from a shutdown state:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status
screen is displayed.
2.
If UPM 4 (FI-UPM) is installed, proceed to Step 3; otherwise, proceed to Step 7.
3.
On the System Status screen, select the
UPM
command. The UPS Control
Command screen screen is displayed.
4.
On the UPS Control Command screen, select the UPM to restart.
5.
Press the
CONTROLS
pushbutton on the UPS Control Command menu bar. The
UPM Control Command screen is displayed.
6.
Proceed to Step 9.
7.
On the System Status screen, select the
UPM
command.
8.
Press the
CONTROLS
pushbutton on the System Status Command menu bar. The
UPM 1 Control Command screen is displayed.
9.
On the UPM Control Command screen, select
UPM ON
.
10.
Press the
SELECT
pushbutton on the UPM Command menu bar.
11.
Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM rectifier and inverter turn on.
12.
To transfer the UPM to Online mode, press the
CONTROLS
pushbutton on the
UPS Control Command menu bar. The UPM Control Command screen is
displayed.
13.
On the UPM Control Command screen, select
UPM GO TO ONLINE
.
14.
Press the
SELECT
pushbutton on the UPM Command menu bar.
The UPM transfers to Online mode. The UPM status indicates
ONLINE
.