Eaton
®
Power Xpert
®
9395P-900 Installation and Operation Manual 164000501—Rev 12
221
c.
Push the washed or new foam filter over the screw heads on the cabinet mounted studs until seated
against the cabinet.
d.
Reinstall the FI-UPM front panel removed in Step c and secure with the retained hardware.
4.
Record maintenance results and any corrective actions in a suitable log.
Figure 141. FI-UPM Air Filter Location
FI-UPM Air Filter
99..22..33
P
PEER
RIIO
OD
DIIC
C M
Maaiinntteennaannccee
Periodic inspections of the UPS should be made to determine if components, wiring, and connections exhibit
evidence of overheating. Particular attention should be given to bolted connections. Maintenance procedures
should specify that the bolted connections be retorqued to values listed in this manual.
99..22..44
A
AN
NN
NU
UA
ALL M
Maaiinntteennaannccee
Annual preventive maintenance should be performed only by authorized service personnel familiar with
maintenance and servicing of the UPS system. Contact an Eaton service representative for more information
about service offerings.
99..22..55
B
BA
ATTTTEER
RYY M
Maaiinntteennaannccee
Contact an Eaton service representative for battery maintenance. Battery replacement and maintenance should
be performed only by authorized service personnel.
Содержание Power Xpert 9395 High Performance
Страница 8: ......
Страница 14: ...xiv Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Table of Contents...
Страница 32: ...12 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Introduction...
Страница 142: ...122 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Installing Options and Accessories...
Страница 149: ...Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 129 Understanding UPS Operation...
Страница 174: ...154 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Understanding UPS Operation...
Страница 236: ...216 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Communication...
Страница 246: ...16400050112 164000501 12...