User Guide DP300E

7OA0001 GB rev.09

DATAPOWER™

DP300E Series
User guide

Copyright © 1997 Silcon Power Electronics A/S

Due to continuous product development information given in this

manual is subject to change without notice.

Summary of Contents for DATAPOWER DP300E series

Page 1: ...e DP300E 7OA0001 GB rev 09 DATAPOWER DP300E Series User guide Copyright 1997 Silcon Power Electronics A S Due to continuous product development information given in this manual is subject to change without notice ...

Page 2: ...2 User Guide DP300E 7OA0001 GB rev 09 ...

Page 3: ...hat to do 6 1 General 6 2 The events stack 6 3 Alarm messages 6 4 The events logger 6 5 Displaying the events stack 7 0 Service bypass switch 7 1 Operating the external service bypass switch 7 2 Operating the external service bypass switch for parallel systems 8 0 Preventive maintenance 8 1 General 8 2 Fan 8 3 Battery 8 4 Battery capacity test 9 0 Economy operation 10 0 Software 10 1 Choice of sof...

Page 4: ...s of a display an alarm LED and a keyboard The display is used for showing parameters measured values and alarm mes sages A background light is activated in case of an alarm or if one of the keys are pressed No activity or no alarm for 5 minutes will automatically switch of the light By pressing and simultaneously you increase the contrast and by pressing and simultaneously you decrease the contra...

Page 5: ...easons the normal user can only switch the UPS into system off mode and from here back into normal operation via the safe push buttons 2 2 Stop Action Display shows Description Open the front door and activate the ON and OFF push button simultaneously 2 3 Start Action Display shows Open the front door and activate the green ON push button Stop start System off Alarm LED lights Acoustic alarm sound...

Page 6: ...o show parameters alarms messages and measured values The alarm LED is used with an audible alarm to indicate unusual operating situations The keyboard is used for programming and control of displaying param eters alarm messages and displaying measured values 3 1 Keyboard description ...

Page 7: ...ge Remote shutdown YES NO Shutdown of UPS by remote signal active Remote shutdown HIGH LOW Nature of remote shutdown signal polarity Remote shutdown time 0 1 2 3 4 Time delay on remote shutdown of UPS 5 6 7 8 9 10 min Battery capacity test Initiates check of back up time The measured time is from start until it reaches low DC warning level See section 8 4 Battery monitor test Initiates check of ba...

Page 8: ... 9 Press to exit Programming of the other parameters can be performed in exactly the same way Bypass operation YES Normal operation load power xx Bypass operation NO 4 2 2 Keys used for programming 4 2 3 Programming example switch to bypass operation Action Display shows 1 Press to enter parameter stack 2 Press or until 3 Press until 4 Press to store Bypass operation NO Bypass operation YES ...

Page 9: ...3 x 385 Vac Mains current is 3 x 16 Aac Battery voltage is 438 Vdc on batt 1 437 Vdc on batt 2 Charging current is 2 Adc Discharging current Output voltage is 3 x 380 Vac Output current is 3 x 15 Aac Output frequency is 50 Hz Battery temperature is 25 C Output peak current is 3 x 22Aac only of interest for service engineers Returns to normal status indication If not pressed automatic switch back w...

Page 10: ...ctive means no back up capacity any longer Call for assistance Battery Week means reduced back up capacity Reset the Battery week alarm signal according to point 4 2 and start up a battery capacity test according to point 8 4 When finished record the obtained back up time and reset an eventual new alarm from the battery monitor Let the UPS recharge the battery for at least 16 hours and with the sa...

Page 11: ...l system Normal operation UPS has been in normal operation Battery operation UPS has been in battery operation Bypass operation UPS has been in bypass operation System off UPS has been off 6 5 Displaying the events stack Action Description 1 Press and 2 Press or 3 Press 4 Press Alarms Press the two keys simultaneously to get access to the events stack Scroll up or down through the events stack las...

Page 12: ...ion 1 above the output switch handle Q002 lights 7 Turn the output switch Q002 to Only the lamp H002 above position 0 the output switch handle Q002 lights now 8 Open the front door and press both the green ON and the red OFF key simultaneously The acoustic alarm sounds for 30 secs 9 Turn the input switch to position 0 The red alarm LED below the display lights and the acoustic alarm sounds for 30 ...

Page 13: ...itch Q002 to position Now the green lamp H003 1 above the bypass switch handle Q003 lights too 9 Turn the bypass switch Q003 to position Only the green lamp H003 0 above the bypass switch handle Q003 lights 10 Press on the keyboard 11 Press or on the keyboard until 12 Press on the keyboard 13 Press on the keyboard 14 Press on the keyboard 15 Press on the keyboard System OFF Normal operation load p...

Page 14: ...ication on the bypass panel The green lamp H003 above the bypass switch handle Q003 lights 6 Turn the external bypass switch Q003 The green lamp H004 to position 1 above the output isolator Q004 and the green lamps H002 above the output switch handles Q002 light 7 Turn the output isolator Q004 to position 0 The green lamp H002 above the output isolator light 8 Turn all output switches Q002 to posi...

Page 15: ...witch EMERGENCY UPS not alive 1 Turn the input switches Q001 to position 0 2 Turn the output switches Q002 to position 0 3 Turn the output isolator Q004 to position 0 4 Change possible released system input fuse s 5 Turn the bypass switch Q003 to position 1 ...

Page 16: ...All systems will transfer to bypass operation 8 Check that green lamp H004 above output isolator Q004 lights 9 Turn the output isolator Q004 to position 1 Now also the green lamp H003 above the bypass switch handle Q003 lights 10 Turn the bypass switch Q003 to position 0 Only the green lamp H003 above the bypass switch handle Q003 lights Point 11 16 must be carried out with same UPS as was used fo...

Page 17: ... Press on the keyboard 12 Press or on the keyboard until 13 Press on the keyboard 14 Press on the keyboard 15 Press on the keyboard No lamps on the bypass panel lights any longer Bypass operation YES Bypass operation NO Normal operation load power xx Display shows ...

Page 18: ... output switch Q002 to position 0 When Q002 is in position 0 the UPS can be operated and tested as a single system without affecting the other parallel UPS s Switching back the UPS to normal parallel redundant operation 1 Turn the input switch Q001 and the output switch Q002 to position 1 2 Charge capacitors connect battery and start up the UPS as described in chapter 5 0 The UPS will automaticall...

Page 19: ...ondition of the battery is checked The result is one of following 1 Battery is OK nothing will happen 2 Battery has reduced capacity Battery week is given 3 Battery capacity far to low Battery defective is given The battery monitoring test is performed by taking out max 25 of the energy in the battery But if the battery monitor is not installed or the exact present back up time has to be checked a...

Page 20: ...arts the battery test To interrupt a running test perform point 1 2 and then press key and xxx is actual obtained back up time in minutes Battery capacity test only Exits the battery capacity test If not operated the system will auto matically exit this program after 30 seconds xxx is back up time from last test if no previous test has been per formed or if the test has been aborted the display wi...

Page 21: ...nd the output voltages and will in case of mains failure switch to battery operation without interruptions The system will in order to keep the batteries fully charged at all times switch to normal operation in a pre programmed sequence The operation of the system is the same as already described in this guide with the exception of the following points When starting up the system will at first go ...

Page 22: ... on the CD 10 2 Configuration code at normal operation Regarding test see further information in guide included on the CD Oper system UNIX VMS Win3 1x Win95 WinNT OS 2 Novell Config code 3 3 8 8 8 8 8 10 3 Choice of cable Operating system Software DP series Cable Windows 3 1x DP SOFT CDX DP300E 0 801 179 Windows 95 Windows NT OS 2 Novell UNIX VMS Windows 3 1x DP SOFT DP300E 0 801 178 Windows 95 Wi...

Page 23: ...3 9239 0 Fax 49 2173 25977 GREAT BRITAIN Silcon Electronics Ltd Milton Court Bredbury Industr Park Horsfield Way Stockport GB Cheshire SK6 2SU Tel 44 0 1614 066 866 Fax 44 0 1614 066 867 IRELAND Gotec Ltd Clonshaugh Industrial Estate IE Dublin 17 Tel 353 1 848 6033 Fax 353 1 848 6040 POLAND Silcon Poland Ltd ul E Orzeszkowej 5 PL 02 374 Warzaw Tel 48 82 26 59 75 01 Fax 48 82 22 23 66 46 SWEDEN Sil...