Power Xpert
®
9395P-900 Installation and Operation Manual 164000501—Rev 12
199
2.
*Verify that the input breakers CB1 are open.
3.
Close all UPS input feeder circuit breakers.
4.
Close all UPS Bypass input feeder circuit breakers.
5.
*Close the CB1 input breakers.
6.
Close the doors and secure the latches.
7.
Observe the UPS control panel becoming active, indicating logic power.
8.
Make sure you are logged in for user access (see
).
9.
Verify no alarms are active.
10. On any UPS, press the
Controls
button on the
Home
screen (see
). The
System Status
screen
is displayed (see
).
11. On the System Status screen, check that the UPS status indicates
Shutdown
.
12. On the System Status screen, select the
Module Controls
button. The Module Controls screen is
displayed (see
). The UPM(s) to start show
Shutdown
(black box).
13. Select the UPM to be started in the left column. The
Module Controls Detail
screen for the UPM appears
(see
14. Press the
Start UPM
button in the Power Status section.
15. Select
Yes
on the confirmation screen.
Verify the following:
•
A message that the selected UPM is starting appears
•
The UPM rectifier and inverter turn on.
•
UPM Power Status line shows
idle
.
•
The UPM status bar shows in a gray color (Idle)
16. Repeat the procedures from step 13 to step 15 to start the other UPMs if required.
NOTE
To transfer to Online mode after starting individual UPMs, follow the procedure in
paragraph
Transfer from Bypass to Online Mode
.
.
77..55..1100 S
Sttaarrttiinngg aa S
Siinnggllee U
UP
PM
M
To start a single UPM:
If required to close a circuit breaker inside a UPS, use appropriate personal protective equipment. Injury to
personnel may occur from electrical shock.
NOTE
UPM 1 is used in this procedure. Use the same procedure to start any UPM as
applicable.
1.
Unfasten the front door latch and swing the door open (see
).
NOTE
*Only perform steps 2 and 5 if the UPS has an input breaker CB1 (see
).
Содержание Power Xpert 9395 High Performance
Страница 8: ......
Страница 14: ...xiv Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Table of Contents...
Страница 32: ...12 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Introduction...
Страница 142: ...122 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Installing Options and Accessories...
Страница 149: ...Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 129 Understanding UPS Operation...
Страница 174: ...154 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Understanding UPS Operation...
Страница 236: ...216 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Communication...
Страница 246: ...16400050112 164000501 12...