Effective March 2013
Instruction Leaflet for Modbus Power Monitoring/
Metering Module (PM3) for FD, JG, and KD/LG
Circuit Breakers and Motor Circuit Protectors
EATON CORPORATION
www.eaton.com
Table 2. FD, JG, KD, LG Terminal Information.
Frame Type
Wire Type
Wire Size
Terminal
Materials
Catalog Number
Torque
AWG
mm
2
Lb.In.
Nm
LG-Frame
Cu/Al
500-750(1)
240-380(1)
Aluminum
TA631L
*2
550
62
LG-Frame
Cu/Al
2-500(2)
35-240(2)
Aluminum
TA632L
*1*2
375
42
LG-Frame
Cu/Al
2-500(1)
35-240(1)
Aluminum
TA350L
375
42
KD-Frame
*3
Cu/Al
2-500(2)
35-240(2)
Aluminum
TA632L
*1*2
375
42
KD-Frame
*3
Cu/Al
2-500(1)
35-240(1)
Aluminum
TA350L
375
42
JG-Frame
Cu/Al
#4-350(1)
25-185
Aluminum
TA250FJ
250
28.2
FD-Frame
Cu/Al
4-40
25-95
Aluminum
3TA225FD
120
13.5
*1
Standard collars mounted on line and load end.
*2
Terminal Shield required.
*3
When using PM3 on KD breakers, LG terminals are required on load end of PM3.
CAUTION
TERMINAL SHIELDS MUST BE USED AS PER ORIGINAL CIRCUIT BREAKER
INSTALLATION INSTRUCTIONS.
Figure 6. Layout of LG 3 Pole with PM3.
q
q
12.135
308.23
2.740
69.60
5.480
139.19
8.438
214.33
13.823
351.10
10.125
257.18
5.577
141.66
4.733
120.22
1.719
43.66
.860
21.84
3.984
101.19
4.062
103.17
5.430
137.92
3.984
101.19
4.062
103.17
4.307
109.40
13.823
351.10
5.577
141.66
2.740
69.60
5.480
139.19
8.438
214.33
12.135
308.23
4.733
120.22
1.719
43.66
.860
21.84