background image

12

Instruction Leaflet 

IL012002EN

Effective March 2013

 Instruction Leaflet for Modbus Power Monitoring/

Metering Module (PM3) for FD, JG, and KD/LG

 Circuit Breakers and Motor Circuit Protectors

EATON CORPORATION

 www.eaton.com

5.Modbus Registers

Slave Actions, Supervisory, and Configuration Commands are 

accomplished through Function Code 16, Write Multiple Registers.  

The Modbus Add-on Module supports three such commands, as 

described in the following sections.

5.1. Add-on Module Status

Status is transmitted in two registers, as shown in Table 6.
Both registers must be accessed in one operation, using Function 

Code 04.

Table 6.  Status Command Description.

Name

Starting Register 

Number (decimal)

Starting Register 

Address (hex)

Number of 

Registers

Format

Status

6145

1800

2

Encoded

Status is encoded as follows: 

• 

Primary Status – High byte of Register Address 0x1800;

• 

Secondary Status – Low byte of Register Address 0x1800; and

• 

Cause of Status – Register Address 0x1801.

Status encoding is shown in Tables 7 thru 9.

Table 7.  Primary Status Codes Table.

Status Code Short Description

4

ALARM

9

OPERATIONAL

Table 8.  Secondary Status Codes Table.

Status Code Short Description

1

NOT APPLICABLE

Table 9.  Cause of Status Codes Table.

Status Code

Short Description

1

Normal

40

DIAGNOSTIC FAILURE #1  (see Note 1 below)

43

DIAGNOSTIC WARNING #2  (see Note 2 below)

44

DIAGNOSTIC WARNING #3  (see Note 3 below)

54

DIAGNOSTIC FAILURE #4  (see Note 4 below)

113

Not Calibrated

Note 1: Measurement Board Communications Failure

Note 2: FRAM Energy Buffer Error 

Note 3: FRAM Calibration Constants Error

Note 4: FRAM Communication Error

5.2. Breaker Status

Breaker Status is transmitted in two discrete (bit) inputs, at address-

es 100110 and 100210.  Both bits may be read in one operation, or 

either bit may be read individually, using Function Code 02.  The 

Function Code 02 format is shown below for a Slave Address of 

0x74.

Table 10.  Request From Master.

Field Name

Slave Address

0x74

Function Code

0x02

Starting Address High Byte

0x03

Starting Address Low Byte

0xE8

Number of Inputs High Byte

0x00

Number of Inputs Low Byte

0x02

CRC Low Byte
CRC High Byte

Table 11.  Response From Slave.

Field Name

Slave Address

0x74

Function Code

0x02

Byte Count

0x01

Data

0x0y (data is in bits 1..0)

CRC Low Byte
CRC High Byte

The Breaker Status command is summarized in Table 12.  Breaker 

Status encoding is shown in Table 13

Table 12.  Breaker Status Command Description.

Name

Starting Register 

Number (decimal)

Starting Register 

Address (hex)

Valid Number 

of Bits

Format

Breaker Status 1001

3E8

1 or 2

Encoded

Breaker Status 1002

3E9

1

Encoded

Table 13.  Breaker Status Encoding.

Register Number (decimal)  Register Address (hex)

Encoding

1001

3E8

0 = Open 

1 = Closed

1002

3E9

0 = Not Tripped 

1 = Tripped

Table 13a.  Combined Breaker Status Encoding  
(Registers 1001 and 1002).

Status Code

Encoding

00

Open

01

Tripped

10

Closed

11 

Unknown *

* Breaker not connected or improperly wired.

Содержание PM3

Страница 1: ... Modbus RTU Communications 10 4 Configuration and Input 11 5 Modbus Registers 12 Appendix A 17 Effective March 2013 Instruction Leaflet IL012002EN Instruction Leaflet for Modbus Power Monitoring Metering Module PM3 for FD JG and KD LG Circuit Breakers and Motor Circuit Protectors ...

Страница 2: ...E PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING Figure 1 Attaching the Endcap Table 1 End Cap Kits Breaker Frame End Cap Kit Cat End Cap Kit Style FD KPEKM1 6606C63G04 FD KPEK1 67B9101G03 JG FJ3RTWK 68C2837G09 JG FJ3RTDK 68C2837G07 KD KPEKM3 5102A14G02 KD KPEK3 5102A14G01 LG L3RTWK 66A4562G05 1 Attach endcap Figure 2 Ins...

Страница 3: ...ION www eaton com Figure 4 Inserting the Screws into the Retainers Figure 5 Torquing the Mounting Screws 4 Insert screws in retainers Torque Chart for Connecting PM3 to Breaker Breaker Frame Head Size Torque FD Slotted screw 34 38 in lb 4 4 4 N m JG Hex 236 120 144 in lb 14 16 N m KD Hex 236 120 144 in lb 14 16 N m LG Hex 315 275 in lb 31 N m 5 Tighten mounting screws to provided torque specificat...

Страница 4: ...75 42 KD Frame 3 Cu Al 2 500 1 35 240 1 Aluminum TA350L 375 42 JG Frame Cu Al 4 350 1 25 185 Aluminum TA250FJ 250 28 2 FD Frame Cu Al 4 40 25 95 Aluminum 3TA225FD 120 13 5 1 Standard collars mounted on line and load end 2 Terminal Shield required 3 When using PM3 on KD breakers LG terminals are required on load end of PM3 CAUTION TERMINAL SHIELDS MUST BE USED AS PER ORIGINAL CIRCUIT BREAKER INSTAL...

Страница 5: ...3 813 96 85 4 062 103 17 4 313 109 55 3 984 101 19 4 89 124 21 5 490 139 45 2 745 69 72 4 062 103 17 2 745 69 72 5 490 139 45 5 766 146 46 13 823 351 10 4 922 125 02 860 21 84 1 719 43 66 8 438 214 33 12 137 308 28 LOAD END LINE END q HANDLE LINE END LOAD END q HANDLE 2X M5 x 0 8 C L 3 952 100 38 11 983 304 37 1 375 34 93 17 48 688 781 19 84 3 171 80 54 5 500 139 70 10 500 266 70 2 063 52 40 4 125...

Страница 6: ...tors EATON CORPORATION www eaton com Figure 9 Layout of FD with PM3 C L C L C L 1 375 34 93 17 45 687 2 875 73 03 4 500 114 30 9 531 242 09 3 625 92 08 6 000 152 40 11 000 279 40 3 501 88 93 3 385 85 98 3 188 80 98 3 625 92 08 3 625 92 08 11 000 279 40 3 344 84 94 3 422 86 92 3 945 100 20 4 125 104 78 1 375 34 93 687 17 45 750 19 05 2 875 73 03 4 500 114 30 9 531 242 09 2 063 52 40 ...

Страница 7: ...solation All inputs and outputs are galvanically isolated to 2500 volts Environmental Ratings Operating temperature 20º to 50 C 4 to 122 F Storage temperature 20º to 50 C 4 to 122 F Operating humidity To 95 RH non condensing Sensing Method Voltage current True RMS Sampling Rate 13 02 K samples per second Update Rate Watts Var and VA 1 03 sec at 60 Hz All other parameters 1 07 second at 60 Hz Power...

Страница 8: ...h a 5 pin Phoenix RA series connector part number 1844249 Figure 10 shows the pin assignments for this connector CAUTION FOR WYE SYSTEM A NEUTRAL IS REQUIRED TO BE CONNECTED TO THE PM3 ON THE RIGHT PHOENIX CONNECTOR IF NEUTRAL IS NOT AVAIL ABLE THE METER WILL CALCULATE A VIRTUAL NEUTRAL BASED ON THE PHASE TO PHASE RMS VOLTAGE THE SYSTEM MUST BE BALANCED FOR THIS TO BE ACCURATE Combination Auxiliar...

Страница 9: ...ne second off indicates the Measurement Board is operating normally Fast Flash 0 5 second on 0 5 second off indicates one of three failures Unit not calibrated Unit has not been assembled properly or Unit memory has been damaged Status RX Led TX Led A B Com DC Common 24 VDC Earth Ground Settings Network Address V Neutral Red Bell Alarm Common Blue Aux Alarm No Connect 2 2 Modbus Status Indicator M...

Страница 10: ...itch Parity even odd none selectable by dip switches 3 1 Modbus RS485 Network The following simplified rules apply to a given system consisting of a cable link between master and slave devices For more complex configurations please refer to standard Modbus RTU wiring specifi cation rules for the RS485 network The recommended Modbus cable has twisted pair wires 24 AWG stranded 7x32 conductors with ...

Страница 11: ...gy Normal Operation 2 ON ABC Left to Right Facing Unit OFF CBA Left to Right Facing Unit 3 4 SW3 ON SW4 ON No Parity 2 Stop Bits SW3 OFF SW4 ON No Parity 1 Stop Bit SW3 ON SW4 OFF Odd Parity 1 Stop Bit SW3 OFF SW4 OFF Even Parity 1 Stop Bit 5 ON 19 2 K BAUD OFF 9600 BAUD 6 ON 120 Ohm Termination Resistor installed OFF No termination Resistor 4 2 Breaker Status The Breaker Status is decoded from tw...

Страница 12: ...IC WARNING 3 see Note 3 below 54 DIAGNOSTIC FAILURE 4 see Note 4 below 113 Not Calibrated Note 1 Measurement Board Communications Failure Note 2 FRAM Energy Buffer Error Note 3 FRAM Calibration Constants Error Note 4 FRAM Communication Error 5 2 Breaker Status Breaker Status is transmitted in two discrete bit inputs at address es 100110 and 100210 Both bits may be read in one operation or either b...

Страница 13: ...er 0x1806 Low Byte Data From Register 0x1807 High Byte Data From Register 0x1807 Low Byte CRC Low Byte CRC High Byte 5 4 Standard Metered Values Standard metered values are transmitted as 32 bit numbers Metered values are read only and are transmitted in two registers Both registers must be accessed in one operation using Function Code 04 Note N The arrangement of the bytes in the 4 byte standard ...

Страница 14: ...Product ID is encoded as follows Product ID 3 b15 b10 of Register Address 0x186F Communication Version 1 b9 b6 of Register Address 0x186F and Division Code 35 b5 b0 of Register Address 0x186F The Breaker Product ID is encoded as follows Product ID 1 b15 b10 of Register Address 0x186E Communication Version 1 b9 b6 of Register Address 0x186E and Division Code 32 b5 b0 of Register Address 0x186E 5 6 ...

Страница 15: ...ccupy consecutive register locations Modbus pro tocol defines register information to be transmitted with the most significant byte first followed by the least significant byte However the protocol does not specify the order of multi register information The default adopted by most of the industry places the least signifi cant word in the first Modbus register x followed by the next higher order 1...

Страница 16: ...the sub functions listed in Table 29 Table 29 Module Supported Sub functions Sub function Code Description Example Transmitted Data Example Received Data 0x0A Clear Diagnostic Counters echo data word 0x55AA 0x55AA 0x0B Read Message Count Diagnostic Counter 0x0000 Message Count 0x0C Read Communications Error Count Diagnostic Counter 0x0000 Communications Error Count 0x0D Read Exception Error Count ...

Страница 17: ...845 1 Int32 4 Apparent Power 3 Phase VA 6191 6192 6190 6191 x182E x182F 1 Uint32 4 Phase A VA 6215 6216 6214 6215 x1846 x1847 1 Uint32 4 Phase B VA 6217 6218 6216 6217 x1848 x1849 1 Uint32 4 Phase C VA 6219 6220 6218 6219 x184A x184B 1 Uint32 4 Power Factor 6195 6196 6194 6195 x1832 x1833 100 Uint32 4 Phase A Power Factor 6227 6228 6226 6227 x1852 x1853 100 Uint32 4 Phase B Power Factor 6229 6230 ...

Страница 18: ...on Leaflet IL012002EN Effective March 2013 Instruction Leaflet for Modbus Power Monitoring Metering Module PM3 for FD JG and KD LG Circuit Breakers and Motor Circuit Protectors EATON CORPORATION www eaton com Notes ...

Страница 19: ...on Leaflet IL012002EN Effective March 2013 Instruction Leaflet for Modbus Power Monitoring Metering Module PM3 for FD JG and KD LG Circuit Breakers and Motor Circuit Protectors EATON CORPORATION www eaton com Notes ...

Страница 20: ...ely for information purposes and should not be considered all inclusive If further information is required you should consult an authorized Eaton sales representative The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties This literature is not intended to and does not...

Отзывы: