Instruction Booklet
Page
14
Effective: July 2010
2-Position Contactor Based
Non-Automatic Transfer Switch
4.6 Voltage Selection Adjustments
Certain devices, such as the Voltage Selection Panel, sensing
relays, and timers, need to be set and/or calibrated prior to plac-
ing the non-automatic transfer switch equipment in service.
Adjustments for logic devices are described in the separate
instructional document dedicated to the specific logic being used.
Voltage selection adjustments are described in this section.
4.6.1 Standard
Voltage Selection
Panels (208, 240, 480,
600 V, - 60 Hz & 220, 380, 415 V, -50
Hz)
The standard voltage selection panel consists of multi-tap trans-
formers, contained in a steel case mounted in the enclosure. To
change the voltage from the factory default 600 Vac, follow the
steps detailed below.
Step 1:
Loosen the six screws securing the cover of the Voltage
Selection Transformer case. Slide the cover up, then
away from the case.
Step 2:
Remove the wires from the primary taps of both trans-
formers and installed them on the taps for the desired
voltage (Figure 12B). Note that only one wire per trans-
former is moved since the second wire is the zero refer-
ence.
Step 3:
Reinstall the cover and tighten the six screws.
Figure 12A. Standard Voltage Selection Panel.
Figure 12B. Standard Voltage Selection Panel.
Figure 12.
CAUTION
BE SURE THAT THE CORRECT VOLTAGE IS SELECTED TO MATCH
THE SYSTEM VOLTAGE. AN IMPROPER SELECTION AND/OR CON-
NECTION COULD RESULT IN EQUIPMENT DAMAGE.
CAUTION
WHEN CHANGING THE VOLTAGE, ONE WIRE MUST BE MOVED ON
THE PRIMARY TAPS OF BOTH TRANSFORMERS.