LMR PLUS Electric Fire Pump Controllers with Transfer Switch
Features

1 - 3

For more information visit: www.chfi re.com

January 2012

FT80 Reduced Voltage - Wye Delta (Star_Delta) Closed

BR05805063K/K

The LMR Plus Electric Fire Pump Controllers meet or exceed the requirements of Under-

writers Laboratories, Underwriters Laboratories Canada, Factory Mutual, the Canadian 

Standards Association, New York City building code, CE mark and U.B.C / C.B.C. Seis-

mic requirements, and are built to NFPA 20 standards.

Standards & Certifi cation

Product Features

Programming Menu

General

The LMR Plus programming menu is 

divided into 8 different sub-menus. Each 

sub-menu contains information relative to 

it’s particular function. A brief description 

of each sub-menu is listed below.

Language

The language sub-menu allows the user 

to select  English, French or Spanish or 

Other languages to be viewed on the LCD 

Display. Several other languages can be 

uploaded into the controller. Contact the 

factory for details. 

Regional

Regional settings include the ability to 

program the date by adjusting the Month, 

Day, Year and Day of Week. As well, the 

Current Time can be adjusted on the 24 

hour clock. 

Pressure

A variety of pressure settings can be 

programmed in the pressure sub-menu. 

These settings include disabling the 

pressure transducer; setting of the start 

point, stop point, low pressure alarm, high 

pressure alarm, stop mode, proof pres-

sure switch (for foam units), low suction 

shutdown (low foam shutdown), pressure 

deviation and hourly pressure recording. 

Refer to the LMR Plus operation manual 

IM05805020K for details.

Timers

Timers in the LMR Plus that can be 

programmed include: Run Period Timer 

(RPT), RPT Start Mode, Acceleration Timer 

(AT), Weekly Test Timer, Fail to Start 

Timer (FST) and Sequential Start Timer 

(SST). Refer to the LMR Plus operation 

manual IM05805020K for details. 

Alarm Set Points

There are fi ve settable alarm points that 

can be programmed by the user. They in-

clude: Phase Rotation, Over Voltage (OV), 

Under Voltage (UV), Over Frequency (OF) 

and Under Frequency (UF). Refer to the 

LMR Plus operation manual IM05805020K 

for details.

Custom Inputs / Outputs

There is provision on the Power I/O Board 

to accept up to 9 additional inputs and 

9 additional outputs. The inputs can be 

labeled using one of 11 pre-set input 

descriptions or assigned a custom descrip-

tion that is programmed by the user. The 

optional outputs can be programmed to 

indicate up to 25 output conditions. As 

well, two optional alarm LED’s can be pro-

grammed for up to 12 alarm conditions.

All optional inputs, outputs and LED’s can 

be linked, as required. 

Inputs can be programmed to energize 

the common alarm output, link to relays 

and optional LED’s and latch until reset 

by the user. Outputs can be programmed 

for fail safe and latch until reset by the 

user. Optional inputs and outputs can be 

programmed with time delay functions.

USB External Drive

General

When using an external USB Drive, the 

drive should conform to the following 

minimum specifi cations:

 

 

                                                     

   Min: 

128mb

                              

Max: 2 Gig  

   FAT16 

protocol

                                       USB 1.0 or 2.0

Drain Valve Solenoid

All LMR Plus electric controllers are 

equipped with a drain valve solenoid used 

for weekly test purposes.

NEMA 2 Enclosures

All LMR Plus controllers come standard 

with NEMA 2 enclosures unless otherwise 

ordered. Available options include: NEMA 

3R, 4, 4X, 12.

Emergency Start Operator

A mechanically operated emergency start 

handle activates the motor contactor inde-

pendent of any electrical control circuits or 

pressure switch input.

Содержание LMR PLUS

Страница 1: ...dicate an absence of an alarm state and energized to indicate the presence of an alarm condition Alarm conditions include Improper Circuit Breaker Operation Motor Operator Failure Lockout Failsafe Con...

Страница 2: ...e controller with the most recent message being displayed first PRINT Menu Description All fault and alarm information is sent to the USB and Printer ports on demand as well as the status of each outp...

Страница 3: ...Run Period Timer RPT RPT Start Mode Acceleration Timer AT Weekly Test Timer Fail to Start Timer FST and Sequential Start Timer SST Refer to the LMR Plus operation manual IM05805020K for details Alarm...

Страница 4: ...For more information visit www chfire com Pump and Plumbing LMR PLUS PLUS MD05805005K B Pump and Plumbing Pump and Plumbing for Fire Pump Controllers March 2010...

Страница 5: ...ary 1 2009 All Limited Service Controllers will not carry FM Approval June 2011 N Y C APPROVED POWER ON PUMP RUNNING LOCAL START REMOTE START DELUGE VALVE EMERGENCY START INTERLOCK ON LOW PRESSURE AUT...

Страница 6: ...r more information visit www chfire com Note For setup and programming information refer to the Operation Manual for the EATON ATC 300 Plus Automatic Transfer Switch Controller IM05805022K MD05805159K...

Страница 7: ...illimeters NOTES 1 All enclosures finished in FirePump red 2 Cable Entrance bottom only 3 Standard Enclosure type NEMA 2 N Y C APPROVED U B C and C B C Must Be Installed Per Applicable Code and Manufa...

Страница 8: ...8 INPUT 9 COMMON ALARM COMMON ALARM PHASE FAILURE NORMALLY ENERGIZED PHASE FAILURE PHASE REVERSAL PHASE REVERSAL FUTURE 1 FUTURE 1 PUMP RUN PUMP RUN NORMALLY ENERGIZED NORMALLY ENERGIZED 2 SETS FORM C...

Страница 9: ...30 40 60 75 1 14 1 0 PER CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 PER CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM PER CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM PER CU AL 2 1 0...

Страница 10: ...0 500MCM PER CU AL For Proper Cable Size Refer to National Electrical Code NFPA 70 LINE VOLTAGE Load Terminals To Motor Qty Cable Sizes 200 208 220 240 380 415 440 480 550 600 Max HP 25 30 40 60 75 1...

Страница 11: ...NGLE VOLTAGE 12 LEAD MOTORS USE LOWER VOLTAGE CONNECTION DIAGRAM Wye Delta Lower Nameplate Voltage Wye Delta Higher Nameplate Voltage NOTE NOTE LMR PLUS Electric Fire Pump Controllers Electric Motor C...

Страница 12: ...g Schematic For more information visit www chfire com ES05805172K C June 2014 Automatic Power Transfer Switch Electrical Wiring Schematic ATC 300 CONTROLLER UTILITY 2 UTILITY 1 CONTROL CIRCUIT ATC 300...

Страница 13: ...ure E5 NEMA 4X 304 Stainless Steel Enclosure E8 Tropicalization 5 20 50 300 500 E9 NEMA 4X Painted Steel 7 5 25 60 350 550 E10 NEMA 4X 316 Stainless Steel Enclosure 10 30 75 400 600 EX Export Crating...

Страница 14: ...or shall be calibrated and set to a minimum of 300 of the mo tor full load current and have a tripping time between 8 and 20 seconds This does not apply to FT20 Limited Service Transfer Switch control...

Страница 15: ...losures 1 NEMA 3R IEC IP14 rain tight enclosure 2 NEMA 4 IEC IP66 watertight enclosure 3 NEMA 4X IEC IP66 watertight 304 stainless steel enclosure 4 NEMA 4X IEC IP66 watertight 316 stainless steel enc...

Страница 16: ...accomplished without the addition of a separate panel or enclosure The LCD display shall indicate low suction shutdown Resetting of the condition shall be automatic or ma nual as selected by the user...

Страница 17: ...Two 2 sets of Form C contacts shall be provided for each of the following 1 Phase Reversal 2 Phase Failure 3 Common Alarm 4 Future 1 5 Pump Run B The Common Alarm and Phase Failure relays shall be en...