LMR  PLUS 

Electric Fire Pump Controllers

Field Connections

For more information visit: 

www.chfire.com

LMR

PLUS 

PLUS 

ES05805099K/D

Field Connections

FD80 Wye Delta (Star-Delta) Closed

Line Terminals (Incoming Cables)

Load Terminals (To Motor)

Typical Controller Connection

NOTE:
1. MOTOR CONNECTIONS VARY, PLEASE 
REFER TO SPECIFIC MOTOR CONNECTION 
DIAGRAM.
2. PLEASE OBSERVE PROPER PHASE 
ROTATION, A,B,C-L1,L2,L3 AS CONTROLLER 
IS PHASE SENSITIVE.
3. CABLE SIZE TO BE 125% OF FULL LOAD 
CURRENT. REFER TO WIRE SIZE TABLE IN 
NFPA 70.

Alarm / Relay Outputs

External Inputs

Qty. & Cable Sizes

200 - 208

220 - 240

380 - 415

440 - 480

550 - 600

Max HP

20

25

30

40

40

(1)#14-#3 PER Ø (CU)

40

50

75

100

100

(1)#14-1/0 PER Ø (CU/AL)

60

75

100

150

150

(1)#6-250MCM PER Ø (CU/AL)

150

150

250

300

300

(2)1/0-250MCM PER Ø (CU/AL)

250

300

500

600

700

(2)2/0-500MCM PER Ø (CU/AL)

* For Proper Cable Size Refer to National Electrical Code NFPA-70

LINE VOLTAGE

Load Terminals (To Motor)

Qty. & Cable Sizes

200 - 208

220 - 240

*380 - 415

440 - 480

550 - 600

Max HP

25

30

40

60

75

(1)#14-1/0 PER Ø (CU/AL)

(1)#14-2/0 (CU/AL)

40

50

75

100

100

(1)#4-4/0 PER Ø (CU)

(1)#4-350MCM (CU/AL)

75

75

150

200

200

(1)#3-350MCM PER Ø (CU/AL)

(1)#4-350MCM (CU/AL)

100

125

200

250

300

(2)3/0-250MCM PER Ø (CU/AL)

(2)1/0-750MCM (CU/AL)

150

200

300

400

400

(2)250-350MCM PER Ø (CU/AL)

(2)1/0-750MCM (CU/AL)

200

-

350

450

550

(2)#1-500MCM PER Ø (CU/AL)

(2)1/0-750MCM (CU/AL)

250

300

500

600

700

(3)3/0-400MCM PER Ø (CU/AL)

(2)1/0-750MCM (CU/AL)

* Coils available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz.

Line Terminals on Main Isolation Switch (Incoming Cables)

LINE VOLTAGE

Service Entrance GND. LUG              
Qty. & Cable Sizes

March 2010

N. Y. C.

APPROVED

 

COMMON ALARM

COMMON ALARM

PHASE FAILURE

(NORMALLY ENERGIZED)

PHASE FAILURE

PHASE REVERSAL

PHASE REVERSAL

FUTURE #1

FUTURE #1

PUMP RUN

PUMP RUN

(NORMALLY ENERGIZED)

(NORMALLY ENERGIZED)

(NORMALLY ENERGIZED)

A

L

A

R

M

C

O

N

T

A

C

T

S

Содержание LMR PLUS

Страница 1: ...dicate an absence of an alarm state and energized to indicate the presence of an alarm condition Alarm conditions include Improper Circuit Breaker Operation Motor Operator Failure Lockout Failsafe Con...

Страница 2: ...e controller with the most recent message being displayed first PRINT Menu Description All fault and alarm information is sent to the USB and Printer ports on demand as well as the status of each outp...

Страница 3: ...Run Period Timer RPT RPT Start Mode Acceleration Timer AT Weekly Test Timer Fail to Start Timer FST and Sequential Start Timer SST Refer to the LMR Plus operation manual IM05805020K for details Alarm...

Страница 4: ...For more information visit www chfire com Pump and Plumbing LMR PLUS PLUS MD05805005K B Pump and Plumbing Pump and Plumbing for Fire Pump Controllers March 2010...

Страница 5: ...ary 1 2009 All Limited Service Controllers will not carry FM Approval June 2011 N Y C APPROVED POWER ON PUMP RUNNING LOCAL START REMOTE START DELUGE VALVE EMERGENCY START INTERLOCK ON LOW PRESSURE AUT...

Страница 6: ...r more information visit www chfire com Note For setup and programming information refer to the Operation Manual for the EATON ATC 300 Plus Automatic Transfer Switch Controller IM05805022K MD05805159K...

Страница 7: ...illimeters NOTES 1 All enclosures finished in FirePump red 2 Cable Entrance bottom only 3 Standard Enclosure type NEMA 2 N Y C APPROVED U B C and C B C Must Be Installed Per Applicable Code and Manufa...

Страница 8: ...8 INPUT 9 COMMON ALARM COMMON ALARM PHASE FAILURE NORMALLY ENERGIZED PHASE FAILURE PHASE REVERSAL PHASE REVERSAL FUTURE 1 FUTURE 1 PUMP RUN PUMP RUN NORMALLY ENERGIZED NORMALLY ENERGIZED 2 SETS FORM C...

Страница 9: ...30 40 60 75 1 14 1 0 PER CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 PER CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM PER CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM PER CU AL 2 1 0...

Страница 10: ...0 500MCM PER CU AL For Proper Cable Size Refer to National Electrical Code NFPA 70 LINE VOLTAGE Load Terminals To Motor Qty Cable Sizes 200 208 220 240 380 415 440 480 550 600 Max HP 25 30 40 60 75 1...

Страница 11: ...NGLE VOLTAGE 12 LEAD MOTORS USE LOWER VOLTAGE CONNECTION DIAGRAM Wye Delta Lower Nameplate Voltage Wye Delta Higher Nameplate Voltage NOTE NOTE LMR PLUS Electric Fire Pump Controllers Electric Motor C...

Страница 12: ...g Schematic For more information visit www chfire com ES05805172K C June 2014 Automatic Power Transfer Switch Electrical Wiring Schematic ATC 300 CONTROLLER UTILITY 2 UTILITY 1 CONTROL CIRCUIT ATC 300...

Страница 13: ...ure E5 NEMA 4X 304 Stainless Steel Enclosure E8 Tropicalization 5 20 50 300 500 E9 NEMA 4X Painted Steel 7 5 25 60 350 550 E10 NEMA 4X 316 Stainless Steel Enclosure 10 30 75 400 600 EX Export Crating...

Страница 14: ...or shall be calibrated and set to a minimum of 300 of the mo tor full load current and have a tripping time between 8 and 20 seconds This does not apply to FT20 Limited Service Transfer Switch control...

Страница 15: ...losures 1 NEMA 3R IEC IP14 rain tight enclosure 2 NEMA 4 IEC IP66 watertight enclosure 3 NEMA 4X IEC IP66 watertight 304 stainless steel enclosure 4 NEMA 4X IEC IP66 watertight 316 stainless steel enc...

Страница 16: ...accomplished without the addition of a separate panel or enclosure The LCD display shall indicate low suction shutdown Resetting of the condition shall be automatic or ma nual as selected by the user...

Страница 17: ...Two 2 sets of Form C contacts shall be provided for each of the following 1 Phase Reversal 2 Phase Failure 3 Common Alarm 4 Future 1 5 Pump Run B The Common Alarm and Phase Failure relays shall be en...

Отзывы: