background image

LMR PLUS Electric Fire Pump Controllers with Transfer Switch
Features

1 - 2

For more information visit: www.chfi re.com

BR05805063K/K

January 2012

FT80 Reduced Voltage - Wye Delta (Star-Delta) Closed

Door Mount

The membrane keypad is accessible from the 
front door of the controller.

NEMA Rating

The standard membrane keypad is rated for 
NEMA 2, 3R, 4, 4X and 12.

 

LCD Display

The Logic Control Board contains a 4 Line by 40 

Characters wide, backlit, LCD display which is 

capable of generating multiple languages.

Alarm & Status LED’s

A total of 20, ( 10 Status - 10 Alarm ) LED’s 

provide indication on the membrane keypad.

Power On

Pump Running

Local Start

Remote Start

Deluge Valve

Emergency Start

Interlock On

Low Pressure

Auto Shutdown Enabled

Programmable LED # 1

Phase Reversal

Phase Failure

Fail To Start

Undervoltage

Overvoltage

Low Room Temperature

Locked Rotor Trip

Low Suction Pressure

Source 2 Disconnected

Programmable LED # 2

Status LED’s

Alarm LED’s

Silence Button

A silence pushbutton on the membrane can 

be used to silence the buzzer. When an alarm 

condition exists, the alarm buzzer will sound. If 

the Silence Alarm button is pressed, the alarm 

buzzer will turn off. If a subsequent alarm con-

dition occurs after the silence button is pressed, 

the buzzer will re-sound. Pressing the Silence 

Alarm button again, will silence the buzzer. 

Motor Test Button

The motor test button on the membrane can be 

used to simulate an automatic start. 

Automatic Shutdown Enabled

When the Automatic Shutdown function is en-

abled, a Green LED will indicate on the control-

ler membrane.

MAIN DISPLAY

General

The main display will show the current system 

pressure, time and date, voltage and amps 

reading for all three phases, the system fre-

quency and any custom messages, alarms or 

timers.

Programmed Set-Point

The set-point display will show programmed 

pressure start point, pressure stop point and 

weekly test timer setting.

Statistics

The statistics display will allow the user to scroll 

through all of the measured statistics stored in 

memory. Refer to LMR Plus operation manual 

IM05805020K for specifi c details.

Diagnostics

The diagnostics display will allow the user to 

scroll thorough eleven diagnostic points to assist 

with troubleshooting the system. 

Message History

The user will be able to scroll through all of 

the messages stored in the memory of the 

controller with the most recent message being 

displayed fi rst.

PRINT Menu

Description

All fault and alarm information is sent to the 

USB and Printer ports on demand, as well as 

the status of each output. The LMR Plus will 

store up to 10K events which are time and date 

stamped. All information can also be retrieved 

and displayed on the LCD display.  

Saving to USB Drive

The controller will save four separate text fi les, 

one CSV fi le and the embedded webpage to the 

USB external drive. The fi les, at maximum size, 

can be saved multiple times on one 128MB USB 

drive.

Files to be saved are: Status Report, Diagnostics 

Report, Statistics Report, Confi guration File and 

Last 10K Messages.

 

Print Menu

The printer menu is accessed in order to select 

the desired print function.

Functions include: Print Messages, Last XX Mes-

sages, Date & Time, Status Report, Diagnostics 

Report and Statistics Report.

Custom Messages

When this item is selected, custom messages 

can be cleared from memory or downloaded 

from the USB external drive.

Firmware Update

Firmware revisions are updated from an ex-

ternal USB drive. All previously programmed 

settings will remain intact when updating is 

completed. Should there be an update failure, 

the controller will automatically revert back to 

the previous version of fi rmware.

Embedded Webpage

General

The embedded webpage is a multifunction tool 

that will allow the user to view the current sta-

tus of the controller as well as display all current 

readings, set points, and history. An external 

computer can be connected via the optional Eth-

ernet port to access the page. When connected, 

the controller set points can be programmed via 

the webpage.

Multiple Pages

There are 5 viewable pages that show the Main 

Display, Statistics, Diagnostics, History and 

Programmed Set Points.

Pressure Points

The pressure reports recorded in memory can 

be graphed and/or sorted based on date and 

time. 

Programmed Set Points

All of the programmed set points and their cur-

rent status can be viewed via the webpage.

Custom Messages

Users can create custom messages on a 

computer and upload to the controller using a 

USB Drive (memory stick). Up to 10 custom 

messages of up to 100 characters each, will 

continuously scroll across the fourth line of the 

LCD display once uploaded.

 

Trigger Points

The message can be programmed to appear at 

specifi c trigger points such as specifi c date and 

time, specifi c number of operations, specifi c 

number of hours run or at any individual alarm 

point.

All of the trigger points can be selected as And/

Or values.

Содержание LMR PLUS

Страница 1: ...dicate an absence of an alarm state and energized to indicate the presence of an alarm condition Alarm conditions include Improper Circuit Breaker Operation Motor Operator Failure Lockout Failsafe Con...

Страница 2: ...e controller with the most recent message being displayed first PRINT Menu Description All fault and alarm information is sent to the USB and Printer ports on demand as well as the status of each outp...

Страница 3: ...Run Period Timer RPT RPT Start Mode Acceleration Timer AT Weekly Test Timer Fail to Start Timer FST and Sequential Start Timer SST Refer to the LMR Plus operation manual IM05805020K for details Alarm...

Страница 4: ...For more information visit www chfire com Pump and Plumbing LMR PLUS PLUS MD05805005K B Pump and Plumbing Pump and Plumbing for Fire Pump Controllers March 2010...

Страница 5: ...ary 1 2009 All Limited Service Controllers will not carry FM Approval June 2011 N Y C APPROVED POWER ON PUMP RUNNING LOCAL START REMOTE START DELUGE VALVE EMERGENCY START INTERLOCK ON LOW PRESSURE AUT...

Страница 6: ...r more information visit www chfire com Note For setup and programming information refer to the Operation Manual for the EATON ATC 300 Plus Automatic Transfer Switch Controller IM05805022K MD05805159K...

Страница 7: ...illimeters NOTES 1 All enclosures finished in FirePump red 2 Cable Entrance bottom only 3 Standard Enclosure type NEMA 2 N Y C APPROVED U B C and C B C Must Be Installed Per Applicable Code and Manufa...

Страница 8: ...8 INPUT 9 COMMON ALARM COMMON ALARM PHASE FAILURE NORMALLY ENERGIZED PHASE FAILURE PHASE REVERSAL PHASE REVERSAL FUTURE 1 FUTURE 1 PUMP RUN PUMP RUN NORMALLY ENERGIZED NORMALLY ENERGIZED 2 SETS FORM C...

Страница 9: ...30 40 60 75 1 14 1 0 PER CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 PER CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM PER CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM PER CU AL 2 1 0...

Страница 10: ...0 500MCM PER CU AL For Proper Cable Size Refer to National Electrical Code NFPA 70 LINE VOLTAGE Load Terminals To Motor Qty Cable Sizes 200 208 220 240 380 415 440 480 550 600 Max HP 25 30 40 60 75 1...

Страница 11: ...NGLE VOLTAGE 12 LEAD MOTORS USE LOWER VOLTAGE CONNECTION DIAGRAM Wye Delta Lower Nameplate Voltage Wye Delta Higher Nameplate Voltage NOTE NOTE LMR PLUS Electric Fire Pump Controllers Electric Motor C...

Страница 12: ...g Schematic For more information visit www chfire com ES05805172K C June 2014 Automatic Power Transfer Switch Electrical Wiring Schematic ATC 300 CONTROLLER UTILITY 2 UTILITY 1 CONTROL CIRCUIT ATC 300...

Страница 13: ...ure E5 NEMA 4X 304 Stainless Steel Enclosure E8 Tropicalization 5 20 50 300 500 E9 NEMA 4X Painted Steel 7 5 25 60 350 550 E10 NEMA 4X 316 Stainless Steel Enclosure 10 30 75 400 600 EX Export Crating...

Страница 14: ...or shall be calibrated and set to a minimum of 300 of the mo tor full load current and have a tripping time between 8 and 20 seconds This does not apply to FT20 Limited Service Transfer Switch control...

Страница 15: ...losures 1 NEMA 3R IEC IP14 rain tight enclosure 2 NEMA 4 IEC IP66 watertight enclosure 3 NEMA 4X IEC IP66 watertight 304 stainless steel enclosure 4 NEMA 4X IEC IP66 watertight 316 stainless steel enc...

Страница 16: ...accomplished without the addition of a separate panel or enclosure The LCD display shall indicate low suction shutdown Resetting of the condition shall be automatic or ma nual as selected by the user...

Страница 17: ...Two 2 sets of Form C contacts shall be provided for each of the following 1 Phase Reversal 2 Phase Failure 3 Common Alarm 4 Future 1 5 Pump Run B The Common Alarm and Phase Failure relays shall be en...

Отзывы: