FT Series Transfer Switches   

                         

 

 

For more information visit:

 www.chfire.com

 

PS05805004K/G 

Fire Pump Controllers 

1-1 

Features

 

Typical Specifications 
1. 

Approvals 

A. 

The Fire Pump Controller and Transfer Switch combi-
nation shall meet the requirements of the latest edition 
of NFPA 20 and shall be listed by [Underwriters Labora-
tories (UL)] and approved by [Factory Mutual] (FM) **, 
[Canadian Standards Association (CSA)] and [New 
York Department of Buildings (NYSB)] for fire pump 
service. 

B. 

The transfer switch shall meet UL 1008 and shall be 
regularly subjected to Endurance, Interrupting Capacity, 
and Dielectric Voltage-Withstand test as outlined by UL 
489 standards. 

2. 

Ratings 

A. 

The transfer switch shall be suitable for the available 
short circuit current at the line terminals of the control-
ler. 

B. 

The transfer switch shall have an ampere rating not 
less than 115% of the motor full-load current. 

3. 

Construction 

A. 

The transfer switch shall be installed in a barriered 
compartment of the fire pump controller. The complete 
assembly, controller and transfer switch, shall be 
shipped as a single unit. 

B. 

A single uni-gear motor shall electrically operate the 
transfer mechanism.  It shall also be capable of being 
operated manually and shall have suitable provisions 
for readily disengaging the gear motor when necessary.   

C. 

The transfer switch shall be mechanically and electrical-
ly interlocked so that it shall not be possible for the load 
circuits to be connected to normal and emergency 
sources simultaneously, regardless of whether the 
switch is electrically or mechanically operated.  The 
switch shall have a manual neutral.  

D. 

The alternate side shall be provided with an isolation 
switch sized to a minimum of 115% of the motor full-
load current and a circuit breaker having a continuous 
current rating not less than 115% of the motor full load 
amps. The isolation switch shall have overcurrent sens-
ing elements of the non-thermal type, and instantane-
ous short-circuit overcurrent protection. (This does not 
apply to FPATS Stand Alone and FT20 Limited Service 
Transfer Switch Controllers.) 
The isolating switch and circuit breaker shall be me-
chanically interlocked and operated by a single handle. 
(This does not apply to FT20 Limited Service Transfer 
Switch Controllers.) 
The isolating switch shall be supervised to indicate 
when it is opened by audible and visual alarms. 

E. 

An auxiliary contact shall be provided to prevent send-
ing of the signal for starting of the alternate source gen-
erator when the transfer switch commands it, if the iso-
lation switch on the alternate source side of the transfer 
switch is open. 

F. 

The transfer switch shall be provided with locked rotor 
overcurrent protection.  The locked rotor protector shall 
be calibrated and set to a minimum of 300% of the mo-
tor full-load current and have a tripping time between 8 
and 20 seconds.(This does not apply to FT20 Limited 
Service Transfer Switch controllers.) 

4. 

Enclosure 

A. 

The controller shall be housed in a NEMA Type 2 (IEC 
IP11) drip-proof, powder baked finish, freestanding en-
closure. 

 

 

5. 

Microprocessor Control 

A. 

A solid state sensing and control logic panel shall be 
separately mounted from the power-switching portion of 
the transfer switch. The two sections shall be connect-
ed together by control cables and plug-in connectors. 
The control section shall be capable of being isolated 
from the power section for maintenance. 

B. 

The normal power source shall be set to pickup at 95% 
and drop out at 85% of nominal supply. The voltage 
sensing on the alternate supply shall be set to pickup at 
95% of nominal voltage. 

C. 

All voltage sensing, frequency sensing, and timer set 
points shall be field adjustable. 

D. 

The transfer switch shall automatically transfer its load 
circuit to an emergency or alternate power supply upon 
failure of the normal or original supply.  In order to over- 
ride momentary fluctuations in the system, a time delay 
transfer from normal to alternate power supply shall be 
adjustable up to 1800 seconds.  Upon restoration of the 
normal supply, the transfer switch shall automatically 
retransfer its load circuits to the normal supply.  Me-
chanically held transfer mechanisms shall be energized 
only momentarily during transfer or retransfer.    

E. 

If the emergency / standby power should fail while car-
rying the load, transfer to the normal supply shall be 
made instantaneously upon restoration of the normal 
source to satisfactory conditions. 

F. 

The transfer switch shall come complete with five LED's 
to provide visual indication of the unit status, source 1 
available, source 1 connected, source 2 available, and 
source 2 connected. 

G. 

An engine test button shall be provided that will initiate 
an engine test. 

H. 

A silence alarm button shall be provided that will silence 
the alarm buzzer. 

6. 

Alarm Relays 

A. 

1 Form-C contact shall be provided for remote indica-
tion for source 1 connected or source 2 connected. 

B. 

2 Form-C contacts shall be provided for remote indica-
tion for the alternate source-isolating switch open. 

7. 

Manufacturer 

A. 

The manufacturer of the assembly shall be the manu-
facturer of major components and control modules in-
stalled within the assembly. 

B. 

The Transfer Switch Fire Pump Controller shall be of 
the LMR Plus type as manufactured by Eaton Industries 
(Canada) Company. 

C. 

Models: 
FT20 Limited Service 
FT30 Across the Line 
FT40 Part Winding 
FT50 Primary Resistor 
FT60 Autotransformer 
FT70 Wye-Delta (Star Delta) Open Transition 
FT80 Wye-Delta (Star Delta) Closed Transition 
FT90 Soft Start 
FPATS Stand Alone Transfer Switch 

 

June 2014 

** NOTE: FPATS Stand Alone and FT20 Limited Service Transfer Switch controllers, do not carry FM Approval. 

Содержание LMR PLUS

Страница 1: ...dicate an absence of an alarm state and energized to indicate the presence of an alarm condition Alarm conditions include Improper Circuit Breaker Operation Motor Operator Failure Lockout Failsafe Con...

Страница 2: ...e controller with the most recent message being displayed first PRINT Menu Description All fault and alarm information is sent to the USB and Printer ports on demand as well as the status of each outp...

Страница 3: ...Run Period Timer RPT RPT Start Mode Acceleration Timer AT Weekly Test Timer Fail to Start Timer FST and Sequential Start Timer SST Refer to the LMR Plus operation manual IM05805020K for details Alarm...

Страница 4: ...For more information visit www chfire com Pump and Plumbing LMR PLUS PLUS MD05805005K B Pump and Plumbing Pump and Plumbing for Fire Pump Controllers March 2010...

Страница 5: ...ary 1 2009 All Limited Service Controllers will not carry FM Approval June 2011 N Y C APPROVED POWER ON PUMP RUNNING LOCAL START REMOTE START DELUGE VALVE EMERGENCY START INTERLOCK ON LOW PRESSURE AUT...

Страница 6: ...r more information visit www chfire com Note For setup and programming information refer to the Operation Manual for the EATON ATC 300 Plus Automatic Transfer Switch Controller IM05805022K MD05805159K...

Страница 7: ...illimeters NOTES 1 All enclosures finished in FirePump red 2 Cable Entrance bottom only 3 Standard Enclosure type NEMA 2 N Y C APPROVED U B C and C B C Must Be Installed Per Applicable Code and Manufa...

Страница 8: ...8 INPUT 9 COMMON ALARM COMMON ALARM PHASE FAILURE NORMALLY ENERGIZED PHASE FAILURE PHASE REVERSAL PHASE REVERSAL FUTURE 1 FUTURE 1 PUMP RUN PUMP RUN NORMALLY ENERGIZED NORMALLY ENERGIZED 2 SETS FORM C...

Страница 9: ...30 40 60 75 1 14 1 0 PER CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 PER CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM PER CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM PER CU AL 2 1 0...

Страница 10: ...0 500MCM PER CU AL For Proper Cable Size Refer to National Electrical Code NFPA 70 LINE VOLTAGE Load Terminals To Motor Qty Cable Sizes 200 208 220 240 380 415 440 480 550 600 Max HP 25 30 40 60 75 1...

Страница 11: ...NGLE VOLTAGE 12 LEAD MOTORS USE LOWER VOLTAGE CONNECTION DIAGRAM Wye Delta Lower Nameplate Voltage Wye Delta Higher Nameplate Voltage NOTE NOTE LMR PLUS Electric Fire Pump Controllers Electric Motor C...

Страница 12: ...g Schematic For more information visit www chfire com ES05805172K C June 2014 Automatic Power Transfer Switch Electrical Wiring Schematic ATC 300 CONTROLLER UTILITY 2 UTILITY 1 CONTROL CIRCUIT ATC 300...

Страница 13: ...ure E5 NEMA 4X 304 Stainless Steel Enclosure E8 Tropicalization 5 20 50 300 500 E9 NEMA 4X Painted Steel 7 5 25 60 350 550 E10 NEMA 4X 316 Stainless Steel Enclosure 10 30 75 400 600 EX Export Crating...

Страница 14: ...or shall be calibrated and set to a minimum of 300 of the mo tor full load current and have a tripping time between 8 and 20 seconds This does not apply to FT20 Limited Service Transfer Switch control...

Страница 15: ...losures 1 NEMA 3R IEC IP14 rain tight enclosure 2 NEMA 4 IEC IP66 watertight enclosure 3 NEMA 4X IEC IP66 watertight 304 stainless steel enclosure 4 NEMA 4X IEC IP66 watertight 316 stainless steel enc...

Страница 16: ...accomplished without the addition of a separate panel or enclosure The LCD display shall indicate low suction shutdown Resetting of the condition shall be automatic or ma nual as selected by the user...

Страница 17: ...Two 2 sets of Form C contacts shall be provided for each of the following 1 Phase Reversal 2 Phase Failure 3 Common Alarm 4 Future 1 5 Pump Run B The Common Alarm and Phase Failure relays shall be en...

Отзывы: