LMR Plus Electric Fire Pump Controllers 

 

July 2011 

For more information visit:

 www.chfire.com

 PS05805008K/E 

Fire Pump Controllers 

1-1 

Features 

Typical Specifications 
 
1. Approvals 

A.  The Fire Pump Controller shall meet the require-

ments of the latest edition of NFPA 20 and shall be 
listed by [Underwriters Laboratories (UL)]and ap-
proved by [Factory Mutual Research (FM)] [Cana-
dian Standards Association (CSA)] [New York De-
partment of Buildings (NYSB)] and carry the CE 
marking for fire pump service. 

2. Starting 

Type 

A.  The controller shall be of the combined manual and 

automatic type designed for [Full Voltage Starting] 
[Part Winding Starting] [Primary Resistor Starting] 
[Autotransformer Starting] [Wye-Delta (Star-Delta) 
Open Transition Starting] [Wye-Delta (Star-Delta) 
Closed Transition Starting] [Solid State Soft Start 
Starting] 

3. Ratings 

A.  The Controller shall have a withstand rating of 

100,000 RMS symmetrical amperes @ [208V] [240V] 
[380V] [400V] [415V] [480V] [25,000 @ 600VAC].  

4. Construction 

A.  The controller shall include a motor rated combina-

tion isolating switch and circuit breaker, mechanically 
interlocked and operated with a single externally 
mounted handle. 

B.  The isolating switch shall be rated to disconnect the 

motor load. 

C.  The isolating switch/circuit breaker combination shall 

be mechanically interlocked such that the enclosure 
door cannot be opened when the handle is in the on 
position except by a tool operated defeater mechan-
ism. 

D. The 

controller 

manufacturer shall manufacture the  

contactor, isolating switch, circuit breaker, pushbut-
tons, and enclosures.  Brand-labeled components 
will not be accepted. 

5.  

Enclosure 

A.  The controller shall be housed in a NEMA Type 2 

(IEC IP11) drip-proof, powder baked finish, frees-
tanding enclosure. 

B. Optional 

Enclosures: 

1.  NEMA 3R (IEC IP14) rain-tight enclosure. 
2.  NEMA 4 (IEC IP66) watertight enclosure. 
3.  NEMA 4X (IEC IP66) watertight 304 stainless 

steel enclosure. 

4.  NEMA 4X (IEC IP66) watertight 316 stainless 

steel enclosure. 

5.  NEMA 4X (IEC IP66) watertight corrosion resis-

tant enclosure. 

6.  NEMA 12 (IEC IP52) dust-tight enclosure. 

 
 
 
 

6. Microprocessor 

Control 

A.  The controller shall come complete with a 4 line by 

40 character LCD display mounted on a panel open-
ing in the front door. The LCD display shall indicate 
the following: 
1.  Main screen displaying system pressure, three-

phase voltage and amperage readings, system 
frequency, date, and time. 

2.  Set point review screen displaying the pro-

grammed pressure start and stop points, and 
weekly test time. 

3.  Controller statistics screen, including: 

a. Powered 

Time 

b.  Motor Run Time 
c. 

Number of Calls to Start 

d.  Number of Starts 
e.  Last Motor Start Time 
f. 

Last Motor Run Time 

g.  Last Low Pressure Start 
h.  Minimum System Voltage 
i. 

Maximum System Voltage 

j. 

Minimum System Frequency 

k. 

Maximum System Frequency 

l. 

Minimum System Pressure 

m.  Maximum System Pressure 
n.  Last System Startup 
o.  Last Phase Failure 
p.  Last Phase Reversal 
q.  Last Locked Rotor Trip  
r. Maximum 

Run 

Current 

s. 

Last Locked Rotor Current 

4.  Controller diagnostics screen, including: 

a.  Date & Time 
b. Firmware 

Version 

c. 

Shop Order Number 

d.  Customer Order Number 
e.  Transformer Output Voltage 
f. 

Current Transformer Outputs 

g.  Pressure Transducer Calibrated Settings 
h. Input 

Status 

i. Output 

Status 

5.  Display last messages screen that will display 

up to 10,000 alarms/messages stored in the 
controllers' memory. 

6.  Display up to ten (10) custom messages of up to 

100 characters each, which will continually scroll 
across the fourth line of the display. 

7.  Remaining time left on active timers. 

B.  The controller shall be supplied with ten  (10) green 

status LED’s for the following: 
1. Power 

On 

2. Pump 

Running 

3. Local 

Start 

4. Remote 

Start 

5. Deluge 

Valve 

6. Emergency 

Start 

Содержание LMR PLUS

Страница 1: ...dicate an absence of an alarm state and energized to indicate the presence of an alarm condition Alarm conditions include Improper Circuit Breaker Operation Motor Operator Failure Lockout Failsafe Con...

Страница 2: ...e controller with the most recent message being displayed first PRINT Menu Description All fault and alarm information is sent to the USB and Printer ports on demand as well as the status of each outp...

Страница 3: ...Run Period Timer RPT RPT Start Mode Acceleration Timer AT Weekly Test Timer Fail to Start Timer FST and Sequential Start Timer SST Refer to the LMR Plus operation manual IM05805020K for details Alarm...

Страница 4: ...For more information visit www chfire com Pump and Plumbing LMR PLUS PLUS MD05805005K B Pump and Plumbing Pump and Plumbing for Fire Pump Controllers March 2010...

Страница 5: ...ary 1 2009 All Limited Service Controllers will not carry FM Approval June 2011 N Y C APPROVED POWER ON PUMP RUNNING LOCAL START REMOTE START DELUGE VALVE EMERGENCY START INTERLOCK ON LOW PRESSURE AUT...

Страница 6: ...r more information visit www chfire com Note For setup and programming information refer to the Operation Manual for the EATON ATC 300 Plus Automatic Transfer Switch Controller IM05805022K MD05805159K...

Страница 7: ...illimeters NOTES 1 All enclosures finished in FirePump red 2 Cable Entrance bottom only 3 Standard Enclosure type NEMA 2 N Y C APPROVED U B C and C B C Must Be Installed Per Applicable Code and Manufa...

Страница 8: ...8 INPUT 9 COMMON ALARM COMMON ALARM PHASE FAILURE NORMALLY ENERGIZED PHASE FAILURE PHASE REVERSAL PHASE REVERSAL FUTURE 1 FUTURE 1 PUMP RUN PUMP RUN NORMALLY ENERGIZED NORMALLY ENERGIZED 2 SETS FORM C...

Страница 9: ...30 40 60 75 1 14 1 0 PER CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 PER CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM PER CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM PER CU AL 2 1 0...

Страница 10: ...0 500MCM PER CU AL For Proper Cable Size Refer to National Electrical Code NFPA 70 LINE VOLTAGE Load Terminals To Motor Qty Cable Sizes 200 208 220 240 380 415 440 480 550 600 Max HP 25 30 40 60 75 1...

Страница 11: ...NGLE VOLTAGE 12 LEAD MOTORS USE LOWER VOLTAGE CONNECTION DIAGRAM Wye Delta Lower Nameplate Voltage Wye Delta Higher Nameplate Voltage NOTE NOTE LMR PLUS Electric Fire Pump Controllers Electric Motor C...

Страница 12: ...g Schematic For more information visit www chfire com ES05805172K C June 2014 Automatic Power Transfer Switch Electrical Wiring Schematic ATC 300 CONTROLLER UTILITY 2 UTILITY 1 CONTROL CIRCUIT ATC 300...

Страница 13: ...ure E5 NEMA 4X 304 Stainless Steel Enclosure E8 Tropicalization 5 20 50 300 500 E9 NEMA 4X Painted Steel 7 5 25 60 350 550 E10 NEMA 4X 316 Stainless Steel Enclosure 10 30 75 400 600 EX Export Crating...

Страница 14: ...or shall be calibrated and set to a minimum of 300 of the mo tor full load current and have a tripping time between 8 and 20 seconds This does not apply to FT20 Limited Service Transfer Switch control...

Страница 15: ...losures 1 NEMA 3R IEC IP14 rain tight enclosure 2 NEMA 4 IEC IP66 watertight enclosure 3 NEMA 4X IEC IP66 watertight 304 stainless steel enclosure 4 NEMA 4X IEC IP66 watertight 316 stainless steel enc...

Страница 16: ...accomplished without the addition of a separate panel or enclosure The LCD display shall indicate low suction shutdown Resetting of the condition shall be automatic or ma nual as selected by the user...

Страница 17: ...Two 2 sets of Form C contacts shall be provided for each of the following 1 Phase Reversal 2 Phase Failure 3 Common Alarm 4 Future 1 5 Pump Run B The Common Alarm and Phase Failure relays shall be en...