Eaton 93PM Integrated Battery Cabinet-Small Welded (IBC-SW) Installation Manual 164000639—Rev 03
29
Figure 11. Top Ventilation
Ventilation
Cover Plate
Grill
Top View
Back View
Front
44..33
IInnssttaalllliinngg P
Poow
weerr W
Wiirriinngg
IBC–SWs can be installed in a line-up-and-match configuration with the power wiring routed through the IBC–
SWs and UPS cabinet or in a standalone configuration with the power wiring routed between the IBC–SWs and
the UPS cabinet using conduit. Use the appropriate procedure for the type of installation being wired.
!
IMPORTANT
This product has been evaluated for use with
copper wire
only
. For external wiring, use only 75°C copper wire.
44..33..11
LLiinnee--U
Upp--aanndd--M
Maattcchh P
Poow
weerr W
Wiirriinngg
NOTE 1
Each battery cabinet will be directly connected to the UPS and not daisy-chained
between cabinets. All power wiring between the IBC–SWs and the UPS is factory
supplied.
NOTE 2
Up to four IBC–SWs can be installed in a line-up-and-match configuration.
Use this procedure to wire line-up-and-match 93PM Integrated Battery Cabinets to the 93PM UPS cabinet.
To install wiring to connections:
1.
Verify the UPS system is turned off and all power sources are removed. Refer to the applicable Eaton
93PM UPS Installation and Operation manual, listed in paragraph
, for UPS
operating procedures.