FC18 FAN CONTROLLER

  

 www.eaton.com

4. Fan controller operation

4.1. Operation process

4.1.1. Manual/auto key switch

A key switch is provided on the front of the Fan Controller 

to enable/disable the buttons on the front fascia. This 

key switch must be kept secure and only accessible by 

authorised personnel who have been trained to use it 

or by the Fire Brigade. The purpose of this key switch is 

to prevent unauthorised activations of fans (i.e. by the 

general public).
If the system enters a fire condition that effects the cause 

and effect rules of the fan controller while it is in manual 

mode it will not activate the fan control outputs but will 

remember the fire condition. Once the fan controller 

is back in the auto mode it will activate the fan control 

outputs as per the fire condition and the cause and  

effect rules.

4.1.2. Key switch in “manual”

When the fan controller key switch is set in manual mode 

it enables the Start/Stop buttons for all 6 channels. The fan 

controller can be placed into manual mode even when the 

system is in a fire condition. This allows the Customer or 

the Fire Brigade to manually activate or deactivate the fan 

associated with each channel of the fan controller.
Pressing the “Start” button will cause the control device 

for that channel to activate which will turn the fan on.  

If the fan has no feedback mechanism then the “On”  

LED will turn on automatically when the “Start” button  

is pressed. If the fan does have a feedback mechanism 

then the fan controller will expect to see the on signal 

from the feedback device within 25s. If the on signal is 

received within the time limit the “On” LED will turn on 

and the “Off” LED will turn off, but if the on signal isn’t 

received then the “Fault” LED will turn on. If the feedback 

signal arrives after the 25s it will result in the “Fault” LED 

to turn off, the “On” LED to be turned on and the “Off” 

LED to turn off to show the current status of the fan.
Pressing the “Stop” button will cause the control device 

for that channel to deactivate which will turn the fan off. 

The fan controller expects to see the off signal from the 

feedback device within 25s. If the off signal is received 

within the time limit the “Off” LED will turn on and the 

“On” LED will turn off, but if the off signal isn’t received 

then the “Fault” LED will turn on. If the feedback signal 

arrives after the 25s it will result in the “Fault” LED to 

turn off, the “Off” LED to be turned on and the “On”  

LED to turn off to show the current status of the fan.

4.1.3. Key switch in “auto”

When the fan controller key switch is set in automatic 

mode it disables the Start/Stop buttons for all 6 channels 

will only allow the channels to be activated by the cause 

and effect programming of the Fire system.
When the Fire system receives a fire alarm signal that 

effects the cause and effect rules of the Fan Controller 

it will turn on the “Fire Activation” LED and activate the 

associated fan as if someone had pressed the start button 

for that channel (see manual Key Switch in “manual”  

for more details).

4.1.4. Fault monitoring

If the fan controller receives a fault condition from either 

the control device or the feedback device (if the fan has 

feedback) it will result in the “Fault” LED turning on.  

This also includes short circuit and open circuit conditions 

between the feedback device and the fan itself.

4.1.5. Reset 

A reset from any panel in the Fire system will not reset 

the Fan Controller itself but may result in the control and 

feedback devices being reset. This will require the Fan 

Controller to be manually reset using the “Reset” button. 

The key switch must be in the manual position in order for 

the reset button to work.

Pressing the “Reset” button will reset the Fan Control 

back to its quiescent condition and all output devices  will 

turn off.

4.1.6. Test LED 

Pressing the “Test LED” button in auto or manual  

mode will cause all of the LEDs to flash 3 times and then 

return to showing the current state of the fan controller 

channels.

 

PR209-166-505-08

   

January 2018

 

Содержание FC18

Страница 1: ...FC18 Fan controller user manual...

Страница 2: ...4 4 1 4 FAULT MONITORING 4 4 1 5 RESET 4 4 1 6 TEST LED 4 5 BASIC SYSTEM LAYOUT 5 5 1 FC18 AND CFC301 ON SAME PANEL AND LOOP 5 5 2 FC18 AND CFC301 ON SAME PANEL BUT DIFFERENT LOOPS 5 5 3 FC18 AND CFC...

Страница 3: ...ot react to evacuations Status LED Power LED Green when Fan Control is working normally the LED on Fire Activation LED Red Operates when fire alarm is received from main panel Controls Key switch Auto...

Страница 4: ...ht click Fan Controller icon Figure 2 Figure 2 Fan controller icon 3 Select Edit Fan Controller to go into the configuration screen Figure 3 4 Once in the configuration screen Select Add Master Figure...

Страница 5: ...M S MCOM FC is located on the system In the Panel Loop and Address icons drop down boxes across from the Confirm select where the feedback device you are going to use CFC301 Technical Input MCIM is lo...

Страница 6: ...current status of the fan Pressing the Stop button will cause the control device for that channel to deactivate which will turn the fan off The fan controller expects to see the off signal from the f...

Страница 7: ...ic system layout 5 1 FC18and CFC301 on same panel and loop Figure 9 5 2 FC6 and CFC301 on same panel but different loops Figure 10 5 3 FC18and CFC301 on differentnetworked panels Figure 11 5 4 FC6 and...

Страница 8: ...ONTROLLER www eaton com FC18 Fan controller user manual 5 5 FC18and MCOM MCIM on same panel but different loops Figure 13 5 6 FC18and MCOM MCIM on different networkedpanels Figure 14 PR209 166 505 08...

Страница 9: ...inimum Nominal Maximum Quiescent current 310 A Environmental Operating temperature 10 C 60 C Humidity Non condensing 95 rh External 24 volt supply 18v 24v 28v External current 150mA Compatibility Suit...

Страница 10: ...on EMEA Headquarters Route de la Longeraie 7 1110 Morges Switzerland Eaton eu Eaton Eaton Electrical Systems Ltd Wheatley Hall Road Doncaster South Yorkshire DN2 4NB United Kingdom 2017 Eaton All Righ...

Отзывы: