3

FC18 Fan controller user manual

FC18 FAN CONTROLLER

  

 www.eaton.com

5. Select the output channel, one to six in the

configuration screen
Select the “Enabled” in the configuration screen

Select the “Loop Mode” in the configuration screen

Select the “Confirm” in the configuration screen

Figure 6. 

In the Panel, Loop and Address icons (drop down boxes) 

across from the Loop Mode, select where the control 

device you are going to use (CFC301 ZMU, MCOM, 

MCOM-S, MCOM-FC) is located on the system.

In the Panel, Loop and Address icons (drop down boxes) 

across from the Confirm, select where the feedback 

device you are going to use (CFC301 Technical Input, 

MCIM) is located on the system. This only needs to be 

set if there is feedback from the fan itself.

If you use 6 channels, you need to open the 6 channels 

which will allow you to write 6 rules.

6. Select in the configuration screen which cause and

effect is needed for the output to activate.

Figure 7. 

Global

By address

By zone group
Select up to 3 stages to have a combination of different 

cause and effect results.

Figure 8. 

 

PR209-166-505-08

 

January 2018

 

Содержание FC18

Страница 1: ...FC18 Fan controller user manual...

Страница 2: ...4 4 1 4 FAULT MONITORING 4 4 1 5 RESET 4 4 1 6 TEST LED 4 5 BASIC SYSTEM LAYOUT 5 5 1 FC18 AND CFC301 ON SAME PANEL AND LOOP 5 5 2 FC18 AND CFC301 ON SAME PANEL BUT DIFFERENT LOOPS 5 5 3 FC18 AND CFC...

Страница 3: ...ot react to evacuations Status LED Power LED Green when Fan Control is working normally the LED on Fire Activation LED Red Operates when fire alarm is received from main panel Controls Key switch Auto...

Страница 4: ...ht click Fan Controller icon Figure 2 Figure 2 Fan controller icon 3 Select Edit Fan Controller to go into the configuration screen Figure 3 4 Once in the configuration screen Select Add Master Figure...

Страница 5: ...M S MCOM FC is located on the system In the Panel Loop and Address icons drop down boxes across from the Confirm select where the feedback device you are going to use CFC301 Technical Input MCIM is lo...

Страница 6: ...current status of the fan Pressing the Stop button will cause the control device for that channel to deactivate which will turn the fan off The fan controller expects to see the off signal from the f...

Страница 7: ...ic system layout 5 1 FC18and CFC301 on same panel and loop Figure 9 5 2 FC6 and CFC301 on same panel but different loops Figure 10 5 3 FC18and CFC301 on differentnetworked panels Figure 11 5 4 FC6 and...

Страница 8: ...ONTROLLER www eaton com FC18 Fan controller user manual 5 5 FC18and MCOM MCIM on same panel but different loops Figure 13 5 6 FC18and MCOM MCIM on different networkedpanels Figure 14 PR209 166 505 08...

Страница 9: ...inimum Nominal Maximum Quiescent current 310 A Environmental Operating temperature 10 C 60 C Humidity Non condensing 95 rh External 24 volt supply 18v 24v 28v External current 150mA Compatibility Suit...

Страница 10: ...on EMEA Headquarters Route de la Longeraie 7 1110 Morges Switzerland Eaton eu Eaton Eaton Electrical Systems Ltd Wheatley Hall Road Doncaster South Yorkshire DN2 4NB United Kingdom 2017 Eaton All Righ...

Отзывы: