2 Engineering
2.1 Fuse protection against short-circuits
Fuse protection against short-circuits can be added to a three-phase supply
system in one of the following ways:
Table 4: Fuse protection EMS-…SWD for IEC applications
Table 5: Fuse protection EMS-… for UL applications
2.2 Derating rated operational current (EMS-…-SWD)
Depending on the installation situation and the maximum ambient air
temperature, it may be necessary to derate the maximum rated operational
current.
Derating is based on the following installation situations:
•
separate mounting,
•
connected in series with 30 mm clearance,
•
without clearance.
Protective
device
I
q
Voltage
Type of
coordination
16A gG/gL
50 kA
500 V
1
30A CCMR 30
50 kA
500 V
1
FAZ-B16/3
2.5 kA
400 V
1
PKM0-4
50 kA
415 V
1
PKM0-6.3
15 kA
415 V
1
Protective
device
SCCR
Voltage
Type of
coordination
20A RK5
5 kA
480 V
–
30A Class CC
100 kA
480 V
–
DANGER
The electronic motor starter must be replaced after a short-
circuit occurs. It is strictly prohibited to keep using it!