3 Commissioning
3.7 Acyclic data
74
Electronic motor starter EMS-...-SWD
12/18 MN034002ZU-DE/EN
www.eaton.com
Object 3 [Index 3]
Byte 0:
Object 4 [Index 4]
Byte 0:
1 Byte
Byte 2
Bit
7
6
5
4
3
2
1
0
Configu-
ration
OL-WARN –
–
–
TYPE
TYPE
TYPE
TYPE
Byte
Bit
Designation
Meaning
0
0 - 3
TYPE
Part no.
4 - 6
–
free
7
OL-WARN
Overload prewarning
0: The computed thermal motor model is less than 105 %
1: The computed thermal motor model is greater than
105%
Bit
7
6
5
4
3
2
1
0
Configu-
ration
I-L1 [%]
I-L1 [%]
I-L1 [%]
I-L1 [%]
I-L1 [%]
I-L1 [%]
I-L1 [%]
I-L1 [%]
Bit
7
6
5
4
3
2
1
0
Configu-
ration
I-L2 [%]
I-L2 [%]
I-L2 [%]
I-L2 [%]
I-L2 [%]
I-L2 [%]
I-L2 [%]
I-L2 [%]
Bit
7
6
5
4
3
2
1
0
Configu-
ration
I-L3 [%]
I-L3 [%]
I-L3 [%]
I-L3 [%]
I-L3 [%]
I-L3 [%]
I-L3 [%]
I-L3 [%]
Data byte
Bit
Designation
Meaning
0
0 - 7
I-L1 [%]
Relative motor current, phase L1
1
0 - 7
I-L2 [%]
Relative motor current, phase L2
2
0 - 7
I-L3 [%]
Relative motor current, phase L3
→
Further information on the subject of “acyclical data transfer” is
provided in the manual MN05013002Z-EN (previous designation
AWB2723-1612en).