3 Commissioning
3.3 Error acknowledgment
Electronic motor starter EMS-...-SWD
12/18 MN034002ZU-DE/EN
www.eaton.com
63
3. Automatically
If output bit 0.3 (RES_AUT) is permanently set, the electronic motor starter
will automatically acknowledge faults after the bi-metal relay is actuated and
the unit goes through a subsequent cool-down period (20 minutes).
DANGER
Automatic restarting may result in bodily injury and/or property
damage.
There is a danger of automatic restarts occurring when the
“automatic reset” operating mode (output bit 0.3 (RES_AUT)
permanently set to 1) is being used.
The unit will restart automatically after the cool-down period of
20 minutes elapses.