Data-Voice-Video 3G Power Solutions (UL-Listed Models)
8
Copyright © 2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-82B May 2011
Battery Mid-point Monitoring Description
Battery Mid-point Monitoring provides a cost-effective method for the early detection of
internal battery faults. The voltages of the two halves of a battery string are measured and the
system controller generates an alarm signal if a voltage imbalance is detected.
A voltage imbalance is an indication that one or more cells has an internal fault. Further
investigation can then isolate the faulty cell(s) and action can be taken to correct the problem
and prevent a total battery failure.
To connect Battery Mid-point Monitoring see details on page
. If a
String Fail
alarm is
generated see Troubleshooting on page
To ensure reliable operation Mid-point Monitoring operates only when the battery is in float
charge and after a configurable lockout period since the last battery discharge, Fast Charge,
Equalize or Battery Test.
Reverse Battery Detect Option
Reverse Battery Detection
detects if a battery has been connected with the incorrect polarity.
Bottom Cable Entry Option
A rear extension cabinet is available for bottom cable entry. See Parts List on page
For details of how to fit the rear extension cabinet, refer to Fit the Rear Extension Cabinet on
page