Start-Up
Copyright © 2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-82B May 2011
47
Parameter
Action
SC200 Navigation*
Float Voltage
Set to the value recommended by
the battery manufacturer.
Control Processes > Voltage
Control > Float Voltage
Battery Capacity Set to the rated 10 hour capacity of
the installed battery strings. Zero
means no battery is installed.
Battery > Battery > Battery
Capacity
Cells Per String
Set to the number of cells in each
battery string.
Battery > Battery > Cells Per
String
Temperature
Compensation
Enable (if required) and check the
settings.
Control Processes > Temp.
Compensation > Enable
Low Voltage
Disconnect (LVD)
Enable (if LVD installed) and check
the settings.
Battery > LVDs > LVD x
System controller
time
Connect using Web to set correct
time manually or connect using
DCTools to synchronize to PC time.
See details in the System Controller
Operation Handbook.
Web: Configuration > Time
DCTools: Configuration >
Identity > Time Synchronization
* Refer to the System Controller Operation Handbook for navigation details (see Related
Information on page
Other configuration settings can be changed after all Start-Up tasks are complete. Refer to the
System Controller Operation Handbook (see Related Information on page
) for details on how
to customize the system's configuration.
Task 5 - Apply DC Power to Battery and Load
Reverse Polarity
Always check that the battery cables have been terminated to the correct system polarity BEFORE
connecting the batteries or closing the battery disconnect device. Connecting batteries to the dc power
system with incorrect system polarity will damage the rectifiers and void all warranty claims.
Step 1 - Check dc voltage and polarity
Check the dc output voltage and polarity of the power system and the
battery string(s).
Step 2 - Connect batteries
1
If connecting multiple battery strings then check the individual strings
are of similar voltage.
2
Close the battery circuit breaker(s).
3
Check the
Battery Fuse Fail
alarm clears.
4
Check the battery current. The actual value depends on the state of
charge of the batteries.