33
totalizer will not have a setpoint, and no output can occur. Once the assignment is
determined, the mode must be selected. There are four modes: timed, latched,
follows, and pulsed, but only certain modes are appropriate for each assignment.
The totalizer setpoint can be timed, in which case the output will turn OFF after a
programmed timeout, or latched, in which case the output will turn OFF after an
unlatch input occurs. Rate low and rate high assignments can be timed or latched,
or can be follows. Follows mode means that the output will turn OFF automatically
when the rate goes back above a rate low setpoint, or below a rate high setpoint. The
rate low/high assignment is follows only. Rate low/high means that the ratemeter
has a low setpoint and a high setpoint; the output is ON when the rate is lower than
the low setpoint or greater than the high setpoint. The output will be OFF whenever
the displayed rate is in the window. The totalizer scaled pulse output mode is called
pulsed. Pulsed is really a timed mode, but instead of selecting an output time in the
range of 0.01 to 99.99 seconds, there are three outputs times from which to choose.
Pulsed fast outputs turn OFF after 500 +/- 84
m
sec, pulsed medium outputs turn OFF
after 2 msec, and pulsed slow outputs turn OFF after 10 msec. If the totalizer is
counting faster than it can spit pulses out, it can store up to 9999 counts in a buffer.
This is great as a temporary fix; however, if this condition is persistent, pick a faster
pulsed output mode.
The batcher only has one programmable output, relay 2. This output can be set to
any of the totalizer assignments mentioned above, or to one of two other assign-
ments unique to batchers. The prewarn setpoint output is a latched mode that is
used for two valve batch delivery and variations thereof. Prewarn operation is de-
scribed on page 5. Finally, the assignment can be cycle setpoint. If this is chosen,
relay 2 will turn ON when the cycle count equals the cycle preset. Cycle setpoint
modes are timed and latched.
Assignment and mode selections are made in programming blocks r1 and r3. If a
timed mode is selected in r1, the timeout is entered into block r2. If a timed mode is
elected in r3, the timeout is entered into r4.
PROGRAMMING cont.