29
Column P - Linear Mode Points
Block
Parameter
Range (default Value is Bold)
P01-A Point 1 Signal
3.00 - 20.00 mA (F6=0)
Level
0.0 - 10.0V (F6=1)
4.00
P01-b Point 1 Rate
0
- 999999
P02-A Point 2 Signal
3.00 -
20.00 mA
(F6=0)
Level
0.0 -
10.0V
(F6=1)
P02-b Point 2 Rate
0 -
999999
P03A-P15b Repeat blocks for signal level and rate for points 3-15 as necessary.
Column P appears in the program mode only if the linearization rate mode is se-
lected in block o1. The number of blocks that show in column P will be twice the
number of points selected in block o4. Starting with the lowest signal level (zero rate
level), enter the signal value and the appropriate flow rate into each set of blocks for
each point. Points must be entered in order, from lowest signal value to highest
signal value.
Column d - defaults
Block ParameterRange (Default Value is Bold)
d1
Power Up Display
0 Last
1 Total low
2 Rate
3 Batch count
4Cycle count
d2
Totalizer Display
0 10 digit total
Mode
1 Totalizer
¸
1
2 Totalizer
¸
10
3 Totalizer
¸
100
d3
Reset Count
0 No reset
Commands
1 Reset totalizer
2 Reset batch count
3 Reset totalizer and batch count
4Reset cycle count
5 Reset totalizer and cycle count
6 Reset cycle and batch counts
7 Reset totalizer, cycle, and batch counts
d4Default Commands
0 No fault
1 Default program values
2 Default run values
3 Default program and run values
PROGRAMMING cont.