66
Instruction Leaflet IL
66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
EATON CORPORATION www.eaton.com
I.L. 66A7638H03
Effective September 2007
66
Configuration Tag 34:
DigiTrip 1150 cv1 >
Command
Number
INCOM
Command
Command
Description
Scan
Level
0
300
Fast Status
Poll
1
301
Primary / Secondary / Cause
Interleaved
2
30F N=3
Current Buffer
Interleaved
3
3C9
Setpoints Buffer
Timed3
4
306
Line-to-Line Voltage Buffer
Interleaved
5
30F N=6
Power Buffer
Interleaved
6
30F N=12
Peak Demand Power Buffer
Interleaved
7
30F N=41
Trip Unit Energy Buffer
Interleaved
Binary
Input
Type
Description
Scan
Level
0
Status
Device On-Line
Virtual
1
Status
Open (S7-S6 state = 00)
Poll
2
Status
Closed (S7-S6 state = 01)
Poll
3
Status
Tripped (S7-S6 state = 10)
Poll
4
Status
LDPU Alarm (S7-S6 state = 11)
Poll
5
Status
Breaker Closed (S6 state)
Poll
6
Status
Remote Trip (S5 state)
Poll
7
Status
Alarms Active (S0 state)
Poll
Analog
Input
Type
Description
Scan
Level
0
Data
I
A
Interleaved
1
Data
I
B
Interleaved
2
Data
I
C
Interleaved
3
Data
I
G
Interleaved
4
Data
I
N
Interleaved
5
Data
V
AB
Interleaved
6
Data
V
BC
Interleaved
7
Data
V
CA
Interleaved
8
Data
Real Power (kW)
Interleaved
9
Data
Reactive Power (kVars)
Interleaved
10
Data
Voltamperes (kVA)
Interleaved
11
Data
PF Apparent (%)
Interleaved
12
Data
Frequency (Hz)
Interleaved
13
Data
Demand (kW)
Interleaved
14
Data
Peak Demand (kW)
Interleaved
15
Data
Demand (kVA)
Interleaved
16
Data
Energy (kWh)
Interleaved
17
Data
Energy (kVAh)
Interleaved