17
Instruction Leaflet IL
66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
EATON CORPORATION www.eaton.com
I.L. 66A7638H03
Effective September 2007
17
Appendix A
DNP V3.00
DEVICE PROFILE DOCUMENT
Vendor Name:
Eaton Corporation
Device Name:
DNP MINT Translator V1.00
Highest DNP Level Supported:
For Requests: DNP-L1 (DNP-L3 without Freeze functionality)
For Responses: DNP-L1 (DNP-L3 without Freeze functionality)
Device Function:
Slave
Maximum Data Link Frame Size:
Received: 292
(octets)
Transmitted:
292
Maximum Application Fragment Size:
Received: 249
(octets)
Transmitted:
1280
Maximum Data Link Retries:
Configurable from 0 to 15 (default set at 0) (Note 1)
Maximum Application Layer Retries:
None
Requires Data Link Confirmation:
Configurable (Note 1)
Requires Application Link Confirmation:
1) When sending multi-fragment responses
(all except final fragment)
2) When reporting Event Data
Timeouts While Waiting For:
Data Link Confirm:
Configurable from 0 to 655.35 seconds (default: 0.50 seconds) (Note 1)
Complete Application Fragment:
None
Application Confirm:
Configurable from 0 to 655.35 seconds (default: 5.00 seconds) (Note 1)
Complete Application Response:
None
Executes Control Operations:
Write Binary Outputs
Never
Select/Operate
Always (Only accepts requests for single CROB object header with:
(Select-to-Operate timeout
Group = 12, Varation = 01, Qualifier = 17
16
or 28
16
,
= 10 seconds)
Latch On/Off, Count = 1, onTime = 0, offTime = 0, Status = 0)
Direct Operate
Always (Only accepts requests for single CROB object header with:
Group = 12, Varation = 01, Qualifier = 17
16
or 28
16
,
Latch On/Off, Count = 1, onTime = 0, offTime = 0, Status = 0)
Direct Operate – No ACK
Always (Only accepts requests for single CROB object header with:
Group = 12, Varation = 01, Qualifier = 17
16
or 28
16
,
Latch On/Off, Count = 1, onTime = 0, offTime = 0, Status = 0)
Count > 1
Never (must = 1)
Pulse On
Never
Pulse Off
Never
Latch On
Always
Latch Off
Always
Queue
Never (must 0 = Normal)
Clear Queue
Never (must 0 = Normal)
Trip / Close
Never (must 00 = NUL)
Reports Binary Input Change Events when no specific variation requested:
Only non-time-tagged
Reports timed-tagged Binary Input Change Events when no specific variation requested:
Never
Sends Unsolicited Responses:
Configurable (default: disabled) (Note 1)
(idle wait time configurable from 0 to 655.35 seconds,
default: 0.50 seconds) (Note 1)
Sends Static Data in Unsolicited Responses:
Never
Default Counter Object/Variation:
Delta and Frozen counters are not implemented.
Counters Roll Over at:
Configurable from 0 through 0FFFFFFFF
16
(Note 1)
Sends Multi-Fragment Responses:
Yes
Additional Notes:
The list of object headers in a read request may not exceed what can be placed into a single frame.
Only Binary Counter 0 (Primary/Secondary/Cause), 1 (Product ID) and Setpoints can produce an event, if assigned to a class.
The “deadband” is set to 0001
16
. All other Binary Counter “deadbands” are set to 0FF (0FFFFFFFF
16
).
Note 1: Configurable by download configuration.