21
Instruction Leaflet IL
66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
EATON CORPORATION www.eaton.com
I.L. 66A7638H03
Effective September 2007
21
Analog
Input
Type
Description
Scan
Level
0
Data
I
A
Interleaved
1
Data
I
B
Interleaved
2
Data
I
C
Interleaved
3
Data
V
NA
Interleaved
4
Data
V
NB
Interleaved
5
Data
V
NC
Interleaved
6
Data
V
TA
Interleaved
7
Data
V
TB
Interleaved
8
Data
V
TC
Interleaved
9
Data
V
PA
Interleaved
10
Data
V
PB
Interleaved
11
Data
V
PC
Interleaved
12
Data
V
P1d
Interleaved
13
Data
V
P1q
Interleaved
14
Data
Real Power (kW)
Interleaved
15
Data
Reactive Power (kVars)
Interleaved
16
Data
PF (%)
Interleaved
17
Data
Temperature (
o
C)
Interleaved
Counter
Input
Type
Description
Scan
Level
0
Data
Primary / Secondary / Cause
Poll
1
Data
INCOM Product ID
Poll
2
Data
Firmware Version / Revision
Timed3
3
Setpoint
System Frequency
Timed3
4
Setpoint
System Voltage
Timed3
5
Setpoint
NWP CT Ratio
Timed3
6
Setpoint
Master Line (0.1V increments)
Timed3
7
Setpoint
Phasing Line (positive degrees, where –5
o
set as 355
o
)
Timed3
8
Setpoint
Phasing Line 1 (positive degrees, where –5
o
set as 355
o
)
Timed3
9
Setpoint
Left Hand Master Line (positive degrees)
Timed3
10
Setpoint
Reverse Trip (0.01% increments)
Timed3
11
Setpoint
Time Delay (1/4 second increments)
Timed3
12
Setpoint
Overcurrent
Timed3
13
Setpoint
Pump Cycles
Timed3
14
Setpoint
Pump Time
Timed3
15
Setpoint
Pump Lockout Reset Delay
Timed3
Control
Output
Latch ON
Latch OFF
0
Open Circuit Breaker and Block Open
Clear Block Open
1
Protective Close
Clear Protective Close
2
Reset Pumping Fault
-----