18
Instruction Leaflet IL
66A7638H03
Effective December 2010
Instructions for DNP MINT Translator Module
Installation and Use
EATON CORPORATION www.eaton.com
I.L. 66A7638H03
Effective September 2007
18
OBJECT
REQUEST
RESPONSE
Grp
Var
Description
FC
Qual Codes
(hex)
FC
Qual Codes
(hex)
1
0
Binary Input: any variation (Def 1)
1
00, 01, 06
129
00, 01
1
1
Binary Input
1
2
00, 01, 06
00, 01, 17, 28 (*)
129
00, 01
(NULL)
1
2
Binary Input with Status
1
00, 01, 06
129
00, 01
2
0
Binary Input Change: any variation (Def 1)
1
06, 07, 08
129
17
2
1
Binary Input Change without time
1
06, 07, 08
129
17
12
1
Control Relay Output Block
3, 4, 5, 6
17, 28
129
echo request
20
0
Binary Counter: any variation (Def 1)
1
00, 01, 06
129
00, 01
20
1
Binary Counter: 32-bit counter
1
00, 01, 06
129
00, 01
20
2
Binary Counter: 16-bit counter
1
00, 01, 06
129
00, 01
20
5
Binary Counter: 32-bit counter without flag
1
2
00, 01, 06
00, 01, 17, 28 (*)
129
00, 01
(NULL)
20
6
Binary Counter: 16-bit counter without flag
1
2
00, 01, 06
00, 01, 17, 28 (*)
129
00, 01
(NULL)
22
0
Counter Change Event: any variation (Def 1)
1
06, 07, 08
129
17
22
1
Counter Change Event: 32-bit without time
1
06, 07, 08
129
17
22
2
Counter Change Event: 16-bit without time
1
06, 07, 08
129
17
30
0
Analog Input: any variation (Def 1)
1
00, 01, 06
129
00, 01
30
1
Analog Input: 32-bit
1
00, 01, 06
129
00, 01
30
2
Analog Input: 16-bit
1
00, 01, 06
129
00, 01
30
3
Analog Input: 32-bit without flag
1
00, 01, 06
129
00, 01
30
4
Analog Input: 16-bit without flag
1
00, 01, 06
129
00, 01
30
5
Analog Input: Short Floating Point
1
00, 01, 06
129
00, 01
32
0
Analog Input Change: any variation (Def 1)
1
06, 07, 08
129
17
32
1
Analog Input Change: 32-bit without time
1
06, 07, 08
129
17
32
2
Analog Input Change: 16-bit without time
1
06, 07, 08
129
17
32
5 (!)
Analog Input Change: Short Float w/o time
1
06, 07, 08
129
17
34
0
Analog Deadband: any variation (Def 2)
1
00, 01, 06
129
00, 01
34
1
Analog Deadband: 16-bit
1
2 (****)
00, 01, 06
00, 01, 17, 28
129
00, 01
(NULL)
34
2
Analog Deadband: 32-bit
1
2 (****)
00, 01, 06
00, 01, 17, 28
129
00, 01
(NULL)
34
3
Analog Deadband: Short Floating Point
1
2 (****)
00, 01, 06
00, 01, 17, 28
129
00, 01
(NULL)
60
1
Class 0 data
1
22
06
06 (*
*
)
129
see BIN, BCNT, AIN
(NULL)
60
2
Class 1 data
1
20, 21, 22
06, 07, 08
06 (
**
)
129
see BIN, BCNT, AIN
(NULL)
60
3
Class 2 data
1
20, 21, 22
06, 07, 08
06 (*
*
)
129
see BIN, BCNT, AIN
(NULL)
60
4
Class 3 data
1
20, 21, 22
06, 07, 08
06 (*
*
)
129
see BIN, BCNT, AIN
(NULL)
80
1
Internal Indicators
1
2
00, 01, 06
00, 01 (**
*
)
129
00, 01
(NULL)
(*)
Function Code 2 supported for Setpoint Objects only (if setpoint write feature for device is configured).
(*
*
)
Function Code 22 sub-headers supported: see BIN, BCNT, AIN Function Code 1.
(**
*
)
Function Code 2 Internal Indicator write supports Range start = 7, end = 7 only.
(****)
Analog Deadbands are stored in non-volatile memory, and are therefore preserved through reset.
(!)
Not Supported for DNP MINT Version 1.00